13
List of warnings and errors
No.
Name
Warning
1
Error
1
Description
1.
Safe..*.
X.
.
Input.Safe.activated
. 2.
Control.signal..
X.
.
Value.of.control.signal.≤.3.mA.
(it applies to ranges 4 – 20/20 – 4 mA)
. 4.
Torque..
X.
.
Induced.torque.beyond.end-limit.positions.or.disconnected.torque.sensor.
. 6.
Thermal.protection..
.
X.
Thermal.protection.input.activated
. 7.
Sense.of.rotation..
.
X.
Reverse.sense.of.rotation.
(for CONTROL only)
. 8.
EEPROM..
X.
.
Wrong.control.sum.of.parameters.in.EEPROM.
. 9.
RAM..
.
X.
Wrong.control.sum.of.parameters.in.RAM.
. 10.
Parameters..
.
X.
Wrong.parameters.in.EEPROM.
. 11.
Setting.regimes..
X.
.
Setting.regime.from.push-buttons.or.PC.
. 12.
Torque.sensor..
.
X.
Disconnected.or.defective.torque.sensor.
. 13.
Sensor.1.
.
X.
Error.of.sensor.of.position.1.
(lowest stage)
. 14.
Sensor.2..
.
X.
Error.of.sensor.of.position.2.
. 15.
Sensor.3.
.
X.
Error.of.sensor.of.position.3.
. 16.
Sensor.4.
.
X.
Error.of.sensor.of.position.4.
(highest stage)
.
. 17.
Calibration..
X.
.
Autocalibration.not.carried.out
. 18.
Torque.setting..
.
X.
Wrong.setting.of.torques
(parameters Torque O/Z 50/100 %)
. 19.
Stroke.
.
X.
Wrong.setting.of.stroke
(parameters Position O/Z)
.
20.. Rotation.error..
.
X..
The.actuator.does.not.rotate
. 21.
High.temperature..
X.
.
Permitted.max..temperature.exceeded.
(parameter Temperature max.)
. 22.
Low.temperature..
X.
.
Permitted.min..temperature.exceeded
(parameter Temperature min.)
. 23.
LCD.internal.*..
X.
.
.Display.of.LCD.internal.does.not.communicate.or.not.added.
in.parameter.CAN.of.configuration.
. 24.
.LCD.external.*.
X.
.
Display.of.LCD.external.does.not.communicate.or.not.added.
.
.
.
.
.
in.parameter.CAN.of.configuration
. 25.
Fieldbus.*.
X.
.
Module.of.industrial.bus.does.not.communicate.or.not.added..
.
.
.
.
.
in.parameter.CAN.of.configuration
. 26.
CAN.*..
X.
.
Error.of.bus.CAN.
(short circuit, interruption, only sensor communicates)
. 27.
Fieldbus.activity*..
X.
.
Connection.to.industrial.bus.not.active.
. 28.
Phase.*.
.
X.
Inverse.order.of.phases.or.some.phase.missing..
. 29.
Relay.of.service.life..
X.
.
Service.life.of.relay.MO/MZ.at.CONTROL.exceeded..
.
.
.
.
.
(parameter.Relay.of.service.life).
. 30.
.Reset..
X.
.
Non-standard.Reset.of.unit.induced.
(watchdog etc.)
.
. 31.
ROM..
.
X.
Wrong.control.sum.of.program.in.ROM..
. 32.
CAN.version.*..
X.
.
Sensor,.LCD.display.or.module.Fieldbus.have.incompatible..
.
.
.
.
.
versions.of.firmware..
. 33.
Wrong.command.*..
.
X.
Commands.Open.and.Close.entered.at.the.same.time.
. 34.
Wrong.inertia.
-.
-.
Wrong.inertia.measured.by.autocalibration
(for autocalibration only)
.. 35.
Wrong.run-down..
-.
-.
Wrong.run-down.measured.by.autocalibration.
(for autocalibration only)
. 41.
Wrong.position..
.
X.
Servo-drive.is.in.position.25.%.behind.working.stroke..
1) Assignment can vary depending on the version of firmware of the sensor control unit.
* Applies to DMS2 only.
Memory of number of induced warnings and errors
–. .For.all.ascertained.warnings.and.errors,.DMS2.ED.uses.counters.of.occurrence.of.these.warnings.and.errors.during.
operation.of.the.system.
–. Values.of.the.counters.are.stored.to.the.EEPROM.memory.and.are.preserved.even.in.case.of.the.power.supply.fall-out..
–. Reading.of.the.counters.is.possible.by.means.of.the.program.for.PC.
–. Clearing.of.the.counters.is.possible.by.means.of.the.program.for.PC.with.the.level.of.authorization.“SERVICE”.
Memory of recently induced warnings and errors
–. DMS2.ED.stores.three.recently.induced.warnings.and.errors.to.the.EEPROM.memory.
–. Recent.warnings.and.errors.can.be.displayed.and.erased.by.means.of.the.program.for.PC..