23
Setting.actuator.by.means.of.push-buttons:
–. Shift.the.change-over.switch.of.local.control.to.position.OFF
–. .Keep. pressing. push-button. STOP. to. enter. the. MENU.. Using. push-buttons. O. or. Z,. browse. through. the. MENU.
(MENU1 – MENU27).
.Shortly.press.push-button.STOP.in.a.selected.menu.to.enter.this.menu.and,.using.push-
buttons.O.or.Z,.select.the.parameter..Keep.pressing.push-button.STOP.to.store.the.parameter.to.memory..Shortly.
press.push-button.STOP.to.exit.the.setting.of.parameters.and.proceed.with.browsing.through.another.menu.
.
Keep.pressing.push-button.STOP.to.exit.the.set.menu;.or.keep.pressing.push-button.STOP.in.the.item.END.after.
the.last.MENU.27.to.terminate.the.setting.regime.
Setting end-limit positions by means of push-buttons of local control
Shift.the.change-over.switch.LOCAL.–.REMOTE.to.position.OFF..Keep.pressing.push-button.STOP.to.enter.the.
setting.regime..Using.push-button.“Z”,.choose.MENU2..Shortly.press.push-button.STOP.to.select.setting.of.position.
“O”..Shift.the.change-over.switch.to.position.“LOCAL”.and.start.the.actuator..After.the.required.position.is.reached,.shift.
the.switch.to.position.“OFF”.and.keep.pressing.of.push-button.“STOP”.to.store.the.position.to.memory..
Shortly.press.push-button.“Z”.to.select.setting.of.position.“Z”..Shift.the.change-over.switch.again.to.position.“LOCAL”.
and.start.the.actuator.in.direction.“Z”..After.the.required.position.is.reached,.shift.the.switch.to.position.“OFF”.and.keep.
pressing.push-button.“STOP”.to.store.the.position.to.memory..
Shortly.press.push-button.“STOP”.to.exit.MENU.2..Keep.pressing.push-button.“STOP”.to.exit.the.setting.regime..
Change.over.the.local.control.to.position.OFF,.enter.the.menu.
(by long pressing of push-button STOP),
.and.
change.over.to.position.“LOCAL”;.the.actuator.can.now.be.shifted.by.means.of.push-buttons.“O”.and.“Z”.beyond.
the.set.end-limit.positions..In.this.case,.the.actuator.will.trip.after.the.set.tripping.torque.is.reached.
Autocalibration
In. the. setting. regime. choose. MENU. 3.. Shortly. press. push-button.“STOP”. to. enter. MENU. 3. and. keep. pressing.
push-button.“STOP”.to.start.autocalibration..By.short.starting.of.the.motor.in.both.directions,.the.actuator.will.measure.
inertia..Completion.of.the..autocalibration.is.announced.by.the.message.AUTOCALIBRATION.OK.
Shortly.press.push-button.“STOP”.to.return.to.MENU.3.and.keep.pressing.of.push-button.“STOP”.to.exit.the.setting.
regime..
Terminal board of the actuator with electronics DMS2 ED
If.the.actuator.is.of.the.single-phase.version.the.power.supply.is.connected.only.to.terminals.
PE, N, U..The.terminals
V, W.remain.non-connected..If.the.actuator.is.of.the.version.“Replacement.of.electric-mechanical.board”.with.three-
phase.electric.motor.without.power.relays,.the.electric.motor.is.connected.to.a.separate.terminal.board.
(not shown
here).