Clearance.at.output.part.. type.no..52.325,.52.326,.52.328.. max..1,5°
.
type.no..52.327,.52.329..
max..2,5°
Protection
The.electric.actuators.are.fitted.with.external.and.internal.protecting.terminal.for.securing.protection.against.
dangerous.shock.voltage..
The.protecting.terminals.are.marked.according.to.ČSN.IEC.417.
(34 5555).
The actuator must be properly secured against both overload and short circuit.
7. ELECTRONIC OUTFIT
Electro-mechanical.control.board.is.replaced.with.the.electronic.system.
DMS2.or.DMS2 ED..Both.systems.scan.
position.of.the.output.shaft.and.torque.of.the.electric.actuator.by.contact-free.magnetic.sensors..Long.service.life.is.
guaranteed.for.the.contact-free.sensors.that.do.not.get.mechanically.worn.
The.sensor.of.the.output.shaft.position.is.absolute.and.does.not.require.any.backup.power.supply.in.case.supply.
voltage.is.disconnected.during.operation.of.the.electric.actuator..Both.systems.can.be.set.and.monitored.by.a.computer.
with.controlling.program.
(set parameter can be backed up on a computer)
.or.manually.without.a.computer.
(for the
electronics DMS2, parameters can be manually set and it can be checked without computer only if the system is
equipped with a display and local control).
.They.contain.diagnostic.functions.-.error.messages.on.the.display,.memory.
of.recent.failures.and.number.of.occurrences.of.respective.failures.
The. more. simple. system.
DMS2 ED. substitutes. the. electro-mechanical. board. and/or. provides. for. controlling..
the.electric.actuator.by.input.analog.signal.as.in.the.version.Control..
The.system
DMS2.enables.the.electric.actuator.to.be.used.for.two-position.and.three-position.regulation.or.to.be.
connected.to.the.industrial.bus.bar.Profibus..
7.1 DMS2 ED
Basic outfit:
Control.unit.
.main.part.of.the.system.DMS2.ED.-.includes.microcomputer,.position.sensor,.3.signal.lamps.LED,.
4.push-buttons.for.simple.setting.and.checking.the.actuator,.connectors.for.connecting.the.torque.
sensor,.source.board,.and.interface.RS.232.
(connection of computer for setting and diagnostics).
Torque.unit
Source.unit..
.electronic.power.supply,.user's.terminal.board.
(connection of power supply and control signals)
,.2.
torque.relays,.2.position.relays,.2.signalling.relays,.1.relay.for.signalling.errors.
(READY),
switch.of.
resistance.anti-condensation.heater,.connectors.for.connecting.electronic.brake,.resistance.heater.
of.analog.module,.and.connector.for.interconnection.with.the.control.unit.
Optional outfit:
Analog.module..
.output.of.feed-back.signal.4.–.20.mA,.in.version.CONTROL.input.of.control.signal.0/4.–.20.mA
Position.indicator.
LED.display
Local.control
Contactors.
Phase.failure.monitoring.. .
module.
.This.module.is.connected.to.all.three.power.phases..If.any.outage.occurs.phase,.the.module.
stops.the.actuator..Outwardly,.this.stop.will.appear.as.an.impulse.thermal.protection.
Parameters:.
Scanning.of.position..
contact-less,.magnetic
Scanning.of.torque..
contact-less,.magnetic
Working.stroke..
see.Tables.1,.2
Torque.blocking..
0.–.20.s.at.reversing.in.limit.positions
Input.signal..
0
(4)
.–.20.mA.with.switched.on.regulator.function
.
Local/Remote.control,.Local.open/close.
Output.signal..
7.x.relay.250.V.AC,.3.A.
(MO, MZ, PO, PZ, SO, SZ, READY)
.
Position.signal.4.–.20.mA.max..500.
Ω
,.active/passive,.galvanic-isolated,.
.
LED.display.
Power.supply.of.electronic. 230.V.AC,.50.Hz,.4.W,.over-voltage.category.II.
7