9
Setting program
The.setting.program.is.same.for.communication.with.the.electronics.DMS2ED.and.DMS2..The.users'.version.can.be.freely.
downloaded..
Note:
In the window “Parameters” of the setting program, column “Access”, the word “NO” designates parameters that cannot
be changed by the user (change of these parameters is blocked).
7.2 PROCEDURE OF SETTING PARAMETERS BY MEANS OF PUSH-BUTTONS
For.simple.programming.of.required.operating.parameters,.the.control.unit.is.fitted.with.four.push-buttons:..
MENU, P, O, C.and.three.signal.lamps.
Yellow
Red
Green
State
.
-.
-.
-.
System.without.feeding
.
-.
-.
lit.on.
Everything.OK.–.working.regime.
(remote, local or switched off control)
.
-.
blinking.
lit.on.
Error.or.warning.–.working.regime.
(remote, local or switched off control)
.
lit.on.
-.
lit.on
.
Enter.or.exit.of.Setting.of.parameters.by.means.of.push-buttons. .
.
.
.
.
.
or.Setting.of.parameters.by.means.of.PC
. blinking.
-.
lit.on
. blinking. blinking.
lit.on.
Setting.of.parameters.by.means.of.push-buttons.
. blinking. blinking.
lit.on
In. adjustment,. follow. the. paragraphs. “VERIFICATION. of. APPARATUS. FUNCTION. And. its. LOCATION”,.
“fitting.on.VALVE”.and.“ADJUSTMENT.of.ACTUATOR.with.VALVE”.of.these.instructions.
For. safety. reasons,. the. system. is. delivered. in. the. state. of. induced. error. of. Calibration. when. the. functions. are.
limited.in.order.to.reduce.the.risk.of.damage.to.the.actuator.by.wrong.wiring..
Record of position CLOSED, OPEN and AUTOCALIBRATION
–. .The.actuator.must.be.adjusted.in.such.a.way.that.the.recorded.position.would.switch.off.the.actuator.before.it.is.swit-
ched.off.by.torque..For.tight.closure,.the.torque.relay.for.torque.Closed.is.only.connected.into.the.control.circuit..The.
actuator.can.be.shifted.either.manually.or.electrically..The.actuator.in.version.CONTROL.can.be.started.from.menu.
MOTOR.in.program.DMS2..In.this.case,.the.actuator.does.not.react.to.the.set.position.and.can.only.be.stopped.by.the.
torque.relay..In.controlling.from.menu.MOTOR,.no.torque.may.be.induced..The.torque.must.be.left.manually..
If,.during.adjustment,.the.torque.is.reached.in.the.end-limit.position,.the.torque.must.be.left.by.means.of.a.hand.wheel..
–. .The.actuator.is.set.to.position.Closed.and.position.Closed.is.stored.by.long.pressing.of.push-button.C.
(without
entering the Menu).
–. .The.actuator.is.set.to.position.Open.and.position.Open.is.stored.by.long.pressing.of.push-button.O..
–. .The.calibration.routine.is.started.by.means.of.push-button.P.
(in remote control)
.that,.in.the.three-position.regulation,.
will.measure.actual.inertial.masses.of.the.system.and.store.them.into.the.memory.of.the.control.unit..In.the.two-
position.regulation,.pressing.of.push-button.P.only.cancels.the.error.of.Calibration.
–. .In.recording.the.end-limit.positions,.signalling.relays.and.the.position.transducer.are.also.set..
–. .In.case.the.actuator.stroke.is.to.be.increased.and.the.switching.off.is.set.to.“from.position”,.the.actuator.will.
switch.off.during.shifting.in.position.O.or.100.%..To.further.change.the.position,.press.C.or.O,.and,.while.
Parametr.–.Parameter
Změna.–.Change
Chyba.–.Error
Přístup.–.Access
Setrvačnost.
(0,1 %)
.–.Inertia.[0.1.%]
Setr..Doběh.
(0,1 s)
.–.Inertial.run-out.[0.1.s]
Necitlivost
(%)
.–.Insensitivity.[%]
NE.–.NO
COM
POWER
TORK
AIN
LED1 LED2 LED3
MENU
P
O
C
Colours of diodes:
LED1.–.yellow.
(menu number)
LED2.–..red.
(parameter value)
LED3.–.green
Push-buttons and signal lamps LED on control unit DMS2.ED.S and DMS2.ED.S90