background image

25

BYPASS DAMPER with INTEGRATED PRESSURE CONTROL 

(Part # STBP or STCDBP)

Bypass  Damper  with  Integrated  Pressure  Control  is  used  to  control  bypass  operations.    The  bypass  damper 

modulates to  maintain static pressure as  zone dampers open and close.  The bypass system reduces air noise 

from the supply registers caused by excessive air velocity.  If the system is configured for intermittent fan mode and 

the system satisfies, there will be a 3-minute delay to allow for system purge, after which the bypass damper will 

open to 25%, preventing noisy rush of air through supply registers when fan starts up on a call for heat or cool.  If 

the  system  is  configured  for  fan  continuous  operation,  the 

STBP

(Round)  or 

STCDBP

(Rectangular)  Electronic 

Bypass will monitor static pressure continuously, providing constant control of system static.

INTEGRATED PRESSURE CONTROL 

DESCRIPTION

A. Supply air tube

B. 24vac R and C

C. Damper Terminal RO, RC, MC

D. LED lights

E. Adjustable Potentiometer

F. TP1 Test Point

Fig. 1

BYPASS DAMPER INSTALLATION

1. Verify  the  bypass  damper  is  sized  properly  to  the 

system and  not  undersized.  (Bypass  damper 

sizing is recommended for 100% of system CFM.)

2. Bypass  damper  and  controller  are powered  by a

dedicated 24vac 40VA transformer.

3. Do not install the bypass damper outside.

4. Locate  the  Integrated  Pressure  Control  (

IPC

) and 

air tube on the bypass damper.

5. Drill  ¼” hole  into  the  side  of  the  supply  duct  2’ 

after the bypass and before the 1

st

supply take-

off.  Mount  pressure  supporting  block  over  ¼”

hole,  align  hole  in  block  with  hole in  duct.  Use 

provided sheet metal screws.

6. Install  air  tube  into  supply  air  duct  by  slipping 

supplied plastic tubing into holes in support block 

and  duct.  Slip  tube  3”  into  the  duct.  Pickup 

tubing fits snugly into provided hole.

7. Connect  pressure  tube  from  static  air  pickup to 

Integrated  Pressure  Controller  (port  closest  to 

you).

Fig. 2

        

BYPASS  DAMPER  WITH  INTEGRATED  BYPASS 

CONTROL SETUP

1. Run all supply dampers to the full open position 

and  have  blower  motor  running  at  100%  fan 

speed.  (See Note #1)

2. Manually  close  the  bypass  damper  by  pressing 

in  the  release  lever  on  the  motor  side  of  the 

actuator.  With the release lever pressed, rotate 

the  damper  actuator  collar  to  close  the  damper 

and release the lever to lock the damper closed.

3.

Quick  Set  Option:   

Turn  the  potentiometer  on 

the damper control board to the full left position 

and  slowly  rotate  RIGHT,  until  the  “RC”  RED 

LED turns on.  Now rotate LEFT just slightly, until 

RC  LED  turns  off.  The 

IPC

is  ready  for 

operation.

RC

” RED LED means damper closing.                         

RO

” GREEN LED means damper opening.

INTEGRATED PRESSURE CONTROL SETUP

Содержание GEN II-R

Страница 1: ...R Installation and Applications Manual Control 2 10 Zones with 2 or 3 Wire Dampers using Standard Thermostats with only 1 Gen II R per System Residential Light Commercial Zoning utilizing 2 postion zo...

Страница 2: ...ntrol board R C Y W OB and E if using emergancy heat in Heat Pump operation 10 Address the the first damper control board jumper as 1 see pages 10 and 11 for thermostat installation and addressing Not...

Страница 3: ...the factory on one pin for normal gas heat operation where the fan is controlled by the HVAC system fan control When a fan output is required from the GEN II R controller on a call for heat place the...

Страница 4: ...g Schematic 4 DAMPER CONTROL BOARD THERMOSTAT SELECTION Round and Rectangular Damper Selection Sizing Sizing Transformer Based on Damper Count Slaving Zone Dampers 10 ZONE DAMPERS 2 OR 3 WIRE SELECTIO...

Страница 5: ...lay fully adjustable capacity control with on board limit settings and optional staging strategies The system provides the installing contractor with a simple startup diagnostic to minimize wiring err...

Страница 6: ...SFORMER 5 TONS AND UNDER OVER 5 TONS BAROMETRIC BYPASS Round 101ABBD diam Rectangular RBB W x H BYPASS DAMPER ELECTRONIC MODULATING BYPASS DAMPER Includes Integrated Static Pressure Control Round STBP...

Страница 7: ...y selected When the GEN II R controller changes modes a 5 minute purge cycle is initiated before the changeover is completed On active heat or cool calls the non calling zones will close When the last...

Страница 8: ...er out to Dampers R C 18 ga thermostat wire TR1 TR2 Damper Power Daisy Chain Damper to Damper 18GA Thermostat wire GAS ELECTRIC OPERATION GEN II R 7 2 SET DN UP S S GND B ON AUTO TIME TMP TIME EH O B...

Страница 9: ...han 40 F 4 C 3 RAISE Press the DN button after C is displayed immediately release the DN button and press the UP button Hold until the desired temperature reading is displayed and release 4 Press the...

Страница 10: ...SET and DN buttons H simultaneously When delay time appears in the display release the buttons and immediately press the DN button and hold until the desired delay time is displayed and release To ve...

Страница 11: ...alibrated to the controller at the factory However the calibration should be checked as part of the system setup procedures If adjustments are required use the Blue potentiometer labeled R44 located i...

Страница 12: ...a 5 minute purge cycle with all supply dampers closing then all dampers modulate open for ventilation GENERAL INSTALLATION INSTRUCTIONS for 5 minutes Heat Pump operation B reversing valve By placing t...

Страница 13: ...oller is configured for Heat Pump HP jumper F on both pins the Cool Heat cut out temperatures are 45 126 F 7 52 C The cut out temperatures can be changed with the following procedure Heat cut out temp...

Страница 14: ...control board must have a unique address from 1 10 To set the damper control board address there is a jumper on the board Find the first damper in the daisy chain and place the jumper on ZN1 for addr...

Страница 15: ...at Cool 7 day programable thermostat Note For heat pump operation with emergency heat install one heat pump thermostat with emergency heat operation on any zone WIRING TO A GAS ELECTRIC THERMOSTAT A A...

Страница 16: ...MPER ZONE DAMPER DM 2 A A B B RC MC RO E Y W OB C R C R ZN1 ZN2 ZN3 ZN4 ZN5 ZN6 ZN7 ZN8 ZN9 ZN10 RUN OPEN RUN CLOSED ZONE DAMPER DM 3 A A B B RC MC RO E Y W OB C R C R ZN1 ZN2 ZN3 ZN4 ZN5 ZN6 ZN7 ZN8...

Страница 17: ...W2 G R HP GE O B R Y1 Y2 G W2 A HP HP HP S S TR1 TR2 TR1 TR2 A A B B RC MC RO E Y W OB C R C R ZN1 ZN2 ZN3 ZN4 ZN5 ZN6 ZN7 ZN8 ZN9 ZN10 RUN OPEN RUN CLOSED HP 24V POWER IN 24V POWER OUT FIELD SUPPLIED...

Страница 18: ...st be connected to the GEN II R TR2 terminal Confirm the daisy chain wiring is correct at this time 3 Check A B wires for proper color code and connections polarity is imperative All A connec tions mu...

Страница 19: ...ycle times out the opposing thermostat call is initiated and the appropriate HVAC outputs are energized and the supply damper opens The thermostat with the opposing call must now satisfy before the GE...

Страница 20: ...r is fully closed and cycle off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RE...

Страница 21: ...s to the maximum static pressure drop in inches of water column between the input upstream of the zone damper and the output downstream when the damper is closed DUCT DIAMETER NOMINAL CFM DUCT VELOCIT...

Страница 22: ...0 7000 7800 8400 9150 10000 10700 11900 13000 13800 14900 15200 16500 17500 30 1500 2100 2700 3425 4200 4950 5700 6350 7150 8400 9150 10000 11000 11800 12400 13800 14200 15000 16000 17400 18500 32 160...

Страница 23: ...ansformer must be sufficient to power the number of dampers used Also a properly rated in line fuse must be used on the secondary of the transformer To determine the power rating of the transformer an...

Страница 24: ...or STCD damper ZONE DAMPER 2 MC RO RC ZONE DAMPER 3 MC RO RC 24 VOLT TRANSFORMER CONTROL RELAY SPST CONTROL RELAY SPST ZONE DAMPER 1 MC RO RC STMPD or STCD damper STMPD or STCD damper STMPD or STCD d...

Страница 25: ...installed in any position The RBB rectangular damper must be installed with horizontal air flow only SIZING When only the smallest zone is calling the maximum amount of excess supply air flow through...

Страница 26: ...Be certain the damper shaft is horizontal c Loosen counter weight with allen wrench d Loosen lever arm from damper shaft and allow to hang straight down e Fully close damper by grabbing damper shaft...

Страница 27: ...r ROUND BYPASS DAMPER SELECTION The Zonex Systems STBP damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION TABLE to confirm the round...

Страница 28: ...4000 4500 5000 5500 6000 14 1167 1458 1750 2042 2333 2625 2917 3208 3500 4083 4667 5250 5833 6417 7000 16 1333 1667 2000 2333 2667 3000 3333 3667 4000 4667 5333 6000 6667 7333 8000 18 1500 1875 2250...

Страница 29: ...a dedicated 24vac 40VA transformer 3 Do not install the bypass damper outside 4 Locate the Integrated Pressure Control IPC and air tube on the bypass damper 5 Drill hole into the side of the supply du...

Страница 30: ...1 To open all dampers it may be necessary to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats This will modulate dampers fully open and lock out compr...

Страница 31: ...ite http www zonexproducts com Part GENII RMAN PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obl...

Отзывы: