3. RAISE – Press the DN button.  After “C” is displayed, immediately release the DN button, and 

press the UP button.  Hold until the desired temperature reading is displayed; then release.

4. Press the DN button to verify the new cool cut-out temperature. 

Adjust 2

nd

Stage Cut-in Time Delay

1. To  increase  the  Y2  and  W2  cut-in  delay,  press  and  hold  the  SET  and  DN  buttons 

(H)

simultaneously.  When 03 appears in the display, release the buttons and immediately press 

the UP button and hold until the desired delay time is displayed, and release. The time delay 

is fully adjustable from 3 - 20 minutes. To verify the change, press and hold the SET and DN 

buttons simultaneously until the delay time is shown, and release. 

2. To  decrease  the  Y2  and  W2  cut-in  delay,  press  and  hold  the  SET  and  DN  buttons 

(H)

simultaneously.  When delay time appears in the display, release the buttons and immediately 

press the DN button and hold until the desired delay time is displayed, and release.  To verify 

the change, press and hold the SET and DN buttons until the delay time is shown, and release. 

Configure Y2 and W2 Cut-in for Time Delay and Thermostat Demand Only

1. Place the 2

nd

stage configuration jumper 

(I)

on the middle and lower pins -

TIME

.

2. If the Y2 cut-in time delay must be changed from the factory setting of 03 (3 min), follow the 

above procedures to raise or lower the time delay value.

NOTE:

The  cut-in  delay  timing  for  W2  (Aux  Heat)  is  set  for  approximately  3  minutes  in  the 

control program and cannot be manually changed.

3. Verify time delay value by pressing the SET and DN buttons simultaneously. 

HEAT PUMP ADVANCED FEATURE CONFIGURATION

GEN II-R

Heat Pump Advanced Feature Configuration 

Heat Pump Capacity Control - Cool and Heat cut-out temperature adjustment

When the 

GEN II-R

controller is configured for Heat Pump (HP jumper 

(F)

on both pins), the Cool /

Heat cut-out temperatures are 45°- 126°F (7°- 52°C).  The cut-out temperatures can be changed 

with the following procedure:

Heat  cut-out  temp 

– To  eliminate  the  possibility  of  the  Heat  Pump  tripping  out  on  high  head 

pressure or short cycling in the heat mode, the heat cut-out temperature should 

never

be changed 

from the factory setting of 126°F (52°C).

1. 

Cool  cut-out  temp

– Press  the  DN  button 

(H)

;  “C”  will  be displayed,  then  the  cut-out 

temperature.

2.   LOWER – Press the DN button.  After the “C” is displayed, continue to hold the DN button until 

the desired temperature is displayed; then release.

NOTE: The controller will not change the Cool cut-out lower than 40°F (4°C).

2nd Stage Heat and Cool Cut-in / Cut-out Configuration

The GEN II-R controller is set up at the factory to stage Y2 and W2 cut-in operation based on a 3-min-

ute time delay and supply air temperature. This is done using the TIME/TEMP (I) jumper. Time may 

be field configured from 3-20 minutes by the contractor during system configuration. The cut-in 

temperatures are fixed in the controller program at 58°F (14°C) and higher for Y2 and 120°F (48°C) 

and lower for W2. The GEN II-R controller second stage cut-out temperature is fixed in the controller 

program at 50°F (10°C). Y2 will de-energize when it drops below 50°F and re-energize when it rises 

above 58°F. If the air temperature drops below the low cut-out (45°F) Y1 and Y2 are de-energized and 

the controller will go into a 5 minute purge mode. After 5 minute purge, if the temperature has risen 

above the low cut-out Y1 is re-energized. Heat W1 and W2 will de-energize if leaving air temperature 

rises above heat cutout and will be locked out for 5 minutes. After 5 minute lockout, if a heat call 

remains and leaving air temperature is lower than heat cutout, W1 will re-energize. By placing jumper 

on bottom two pins, a time only strategy may be configured into the system. ( see below);

E

Y

W/OB

C

R

C

R

Содержание GEN II-R

Страница 1: ...R Installation and Applications Manual Control 2 10 Zones with 2 or 3 Wire Dampers using Standard Thermostats with only 1 Gen II R per System Residential Light Commercial Zoning utilizing 2 postion zo...

Страница 2: ...ntrol board R C Y W OB and E if using emergancy heat in Heat Pump operation 10 Address the the first damper control board jumper as 1 see pages 10 and 11 for thermostat installation and addressing Not...

Страница 3: ...the factory on one pin for normal gas heat operation where the fan is controlled by the HVAC system fan control When a fan output is required from the GEN II R controller on a call for heat place the...

Страница 4: ...g Schematic 4 DAMPER CONTROL BOARD THERMOSTAT SELECTION Round and Rectangular Damper Selection Sizing Sizing Transformer Based on Damper Count Slaving Zone Dampers 10 ZONE DAMPERS 2 OR 3 WIRE SELECTIO...

Страница 5: ...lay fully adjustable capacity control with on board limit settings and optional staging strategies The system provides the installing contractor with a simple startup diagnostic to minimize wiring err...

Страница 6: ...SFORMER 5 TONS AND UNDER OVER 5 TONS BAROMETRIC BYPASS Round 101ABBD diam Rectangular RBB W x H BYPASS DAMPER ELECTRONIC MODULATING BYPASS DAMPER Includes Integrated Static Pressure Control Round STBP...

Страница 7: ...y selected When the GEN II R controller changes modes a 5 minute purge cycle is initiated before the changeover is completed On active heat or cool calls the non calling zones will close When the last...

Страница 8: ...er out to Dampers R C 18 ga thermostat wire TR1 TR2 Damper Power Daisy Chain Damper to Damper 18GA Thermostat wire GAS ELECTRIC OPERATION GEN II R 7 2 SET DN UP S S GND B ON AUTO TIME TMP TIME EH O B...

Страница 9: ...han 40 F 4 C 3 RAISE Press the DN button after C is displayed immediately release the DN button and press the UP button Hold until the desired temperature reading is displayed and release 4 Press the...

Страница 10: ...SET and DN buttons H simultaneously When delay time appears in the display release the buttons and immediately press the DN button and hold until the desired delay time is displayed and release To ve...

Страница 11: ...alibrated to the controller at the factory However the calibration should be checked as part of the system setup procedures If adjustments are required use the Blue potentiometer labeled R44 located i...

Страница 12: ...a 5 minute purge cycle with all supply dampers closing then all dampers modulate open for ventilation GENERAL INSTALLATION INSTRUCTIONS for 5 minutes Heat Pump operation B reversing valve By placing t...

Страница 13: ...oller is configured for Heat Pump HP jumper F on both pins the Cool Heat cut out temperatures are 45 126 F 7 52 C The cut out temperatures can be changed with the following procedure Heat cut out temp...

Страница 14: ...control board must have a unique address from 1 10 To set the damper control board address there is a jumper on the board Find the first damper in the daisy chain and place the jumper on ZN1 for addr...

Страница 15: ...at Cool 7 day programable thermostat Note For heat pump operation with emergency heat install one heat pump thermostat with emergency heat operation on any zone WIRING TO A GAS ELECTRIC THERMOSTAT A A...

Страница 16: ...MPER ZONE DAMPER DM 2 A A B B RC MC RO E Y W OB C R C R ZN1 ZN2 ZN3 ZN4 ZN5 ZN6 ZN7 ZN8 ZN9 ZN10 RUN OPEN RUN CLOSED ZONE DAMPER DM 3 A A B B RC MC RO E Y W OB C R C R ZN1 ZN2 ZN3 ZN4 ZN5 ZN6 ZN7 ZN8...

Страница 17: ...W2 G R HP GE O B R Y1 Y2 G W2 A HP HP HP S S TR1 TR2 TR1 TR2 A A B B RC MC RO E Y W OB C R C R ZN1 ZN2 ZN3 ZN4 ZN5 ZN6 ZN7 ZN8 ZN9 ZN10 RUN OPEN RUN CLOSED HP 24V POWER IN 24V POWER OUT FIELD SUPPLIED...

Страница 18: ...st be connected to the GEN II R TR2 terminal Confirm the daisy chain wiring is correct at this time 3 Check A B wires for proper color code and connections polarity is imperative All A connec tions mu...

Страница 19: ...ycle times out the opposing thermostat call is initiated and the appropriate HVAC outputs are energized and the supply damper opens The thermostat with the opposing call must now satisfy before the GE...

Страница 20: ...r is fully closed and cycle off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RE...

Страница 21: ...s to the maximum static pressure drop in inches of water column between the input upstream of the zone damper and the output downstream when the damper is closed DUCT DIAMETER NOMINAL CFM DUCT VELOCIT...

Страница 22: ...0 7000 7800 8400 9150 10000 10700 11900 13000 13800 14900 15200 16500 17500 30 1500 2100 2700 3425 4200 4950 5700 6350 7150 8400 9150 10000 11000 11800 12400 13800 14200 15000 16000 17400 18500 32 160...

Страница 23: ...ansformer must be sufficient to power the number of dampers used Also a properly rated in line fuse must be used on the secondary of the transformer To determine the power rating of the transformer an...

Страница 24: ...or STCD damper ZONE DAMPER 2 MC RO RC ZONE DAMPER 3 MC RO RC 24 VOLT TRANSFORMER CONTROL RELAY SPST CONTROL RELAY SPST ZONE DAMPER 1 MC RO RC STMPD or STCD damper STMPD or STCD damper STMPD or STCD d...

Страница 25: ...installed in any position The RBB rectangular damper must be installed with horizontal air flow only SIZING When only the smallest zone is calling the maximum amount of excess supply air flow through...

Страница 26: ...Be certain the damper shaft is horizontal c Loosen counter weight with allen wrench d Loosen lever arm from damper shaft and allow to hang straight down e Fully close damper by grabbing damper shaft...

Страница 27: ...r ROUND BYPASS DAMPER SELECTION The Zonex Systems STBP damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND BYPASS SELECTION TABLE to confirm the round...

Страница 28: ...4000 4500 5000 5500 6000 14 1167 1458 1750 2042 2333 2625 2917 3208 3500 4083 4667 5250 5833 6417 7000 16 1333 1667 2000 2333 2667 3000 3333 3667 4000 4667 5333 6000 6667 7333 8000 18 1500 1875 2250...

Страница 29: ...a dedicated 24vac 40VA transformer 3 Do not install the bypass damper outside 4 Locate the Integrated Pressure Control IPC and air tube on the bypass damper 5 Drill hole into the side of the supply du...

Страница 30: ...1 To open all dampers it may be necessary to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats This will modulate dampers fully open and lock out compr...

Страница 31: ...ite http www zonexproducts com Part GENII RMAN PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obl...

Отзывы: