ZMC408SCAN Motion Controller Hardware Manual V1.5
→
Wiring Note:
ZMC408SCAN controller uses the single power, and ZIO expansion module uses
dual-power. When using, main power supply of expansion module and main power
supply of controller can share one power. When they use different power supplies,
controller power EGND needs to connect to expansion module power GND, otherwise
CAN may be burnt out.
When connecting multiple ZIO expansion modules on the CAN bus, a 120-ohm
resistor needs to be connected in parallel between the CANL and CANH terminals, for
the ZIO expansion module that is with 8-digit dialing codes, the terminal resistor can
be realized by dialing the code (DIP).
Содержание ZMC408SCAN
Страница 1: ......
Страница 52: ...ZMC408SCAN Motion Controller Hardware Manual V1 5 Wiring reference of terminal s 12 DA...