p.
57/61
temperature of
the flue gases (if
flue gas
thermometer is
mounted)
exchanging
surfaces of the heat
consumer are
deposited with ash,
presenting heat
resistive layer, thus
decreasing the heat
exchanging
intensity
the heat consumer surfaces in order
to decrease ash layer heat resistance;
22.
Flue gases are
emitted out of
the heat
consumer unit
after certain
period of
exploitation
The flue gas duct
is clogged or even
blocked by fly ash
deposits
It is necessary to clean thoroughly
the heat consumer’s flue gas duct as
well as chimney
;
23.
Other failures,
not described
above
It is necessary to consult authorized
technician and eventually service
maintenance should be performed
Table 5.4.
Automatic pellet burner of series “GP” faults and repair procedures
.
EXPLANATION :
*:
the overheating of the pellet delivery pipe is most commonly due to increased
ash deposition layer on the heat exchanging surfaces on the appliance, on which
the burner is installed;
** in case of deficiency of chimney’s draught, it is recommended to ask for
service assistance in order to solve the problem – it could be possible to make
thorough cleaning of the chimney or even to make reconstruction of the
chimney, also installation of additional flue gas fan could be an appropriate
technical solution – any of these should be done by service technician as well;