p.
25/61
5.
Initial steps and starting of pellet burner of series “GP”
Attention :
The burner should be installed, adjusted and verified ONLY by
trained staff of an authorized company.
5.1.
Basic fuel requirements
The fuel should be dry. The unit producer recommends that the fuel
should be stored in dry and well ventilated rooms;
It is strongly forbidden to store the fuel in close region of the unit, on
which the pellet burner is installed, the minimal safety distance between
the fuel and the appliance is 400 mm;
The burner producer recommends an optimal distance between the unit,
on which the pellet burner is installed, and the fuel bunker to be at least
1000mm. It is recommended to store the fuel in room, next to that, where
the system is installed;
At the installation procedure of the burner, as well as the fuel storage one,
fire prevention recommendation should be considered. It is also
recommended to install a fire-extinguisher in a safe and easy accessible
place;
5.2.
Staring automatic pellet burner of series “GP”
Basic requirements :
Any maintenance procedures should be performed in accordance with the
described in this manual;
The operating mode of a system
: automatic pellet burner of series “GP”
and a heat-consumer
, should also cover the following requirement : the
operating pressure in the combustion chamber
should be below
the atmosphere pressure
within the following range: 5 - 20 Pa.
The incompleteness of this requirement could lead to alarm
modes of the burner and/or ineffective operation regime of the
burner. The operating pressure in the combustion chamber of the
heat-consumer strongly depends on the draught of the flue stack as well as
the hydraulic loses in the gas duct of the system (as well as the operation of
induced draught flue gas fan module installed);
Any intervention in the working process of the unit, which could lead to
unit’s failure and/or dangerous and health threatening situations, are strongly
prohibited;
The unit should be checked by the maintenance staff or any trained
personal/end user regularly;