Chapter 10. Receiving Tests
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
10-12
10.8
Installation
10.8.1
Location
The location where the Terminal Unit is to be installed should meet the following minimum
conditions to ensure correct operation, long service life, ease of installation and ease of
maintenance:
Absence of dust
Absence of vibration
Easy access
Absence of dampness
Adequate lighting
Horizontal mounting
Mounting should be in accordance with the instructions regarding installations in the dimension
diagram.
10.8.2
Connection
Terminals C1 and F1 (or K1, X1 depending on the model) should be solidly grounded to ensure
disturbance-filtering circuits operate properly. The wire used for grounding these terminals
should be stranded 14 AWG. Ground wire length should be minimized and should not exceed
12”. The ground terminal of the enclosure located on the rear panel of the equipment should
also be grounded.