Chapter 5. Settings
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
5-6
Recloser Enable (7IRD-A Model)
Setting
Range
Phase to Phase tripped by Phase Instantaneous (IF)
YES / NO
Phase to Phase tripped by Phase Time (TF)
YES / NO
To Ground tripped by Ground Instantaneous (IN)
YES / NO
To Ground tripped by Ground Time (TN)
YES / NO
Open Phase (FA)
YES / NO
Residual Current (DN)
YES / NO
External Protection Actuation (PE)
YES / NO
Recloser Enable (7IRD-J Model)
Setting
Range
Phase to Phase tripped by Phase 1 Instantaneous (I1F)
YES / NO
Phase to Phase tripped by Phase Time (TF)
YES / NO
To Ground tripped by Ground 1 Instantaneous (I1N)
YES / NO
To Ground tripped by Ground Time (TN)
YES / NO
Open Phase (FA)
YES / NO
Residual Current (DN)
YES / NO
External Protection Actuation (PE)
YES / NO
Recloser Status for these Settings
Reclose for Trips with Recloser Reset
Reclose after Reset Timer is Active after 1st, 2nd, 3rd or 4th Reclose Attempt
5.1.5
Logic Settings
Logic
Setting
Range
Step
Trip Output Seal-in Enable
YES / NO
Breaker Open Failure Time
0.02 - 2s
0.01s
Breaker Close Failure Time
0.02 - 2s
0.01s
Recloser Close Enable
YES / NO
Содержание 7IRD-A
Страница 2: ......
Страница 164: ......
Страница 165: ......
Страница 166: ......
Страница 167: ......
Страница 168: ......
Страница 169: ......
Страница 170: ......
Страница 171: ......
Страница 172: ......
Страница 173: ......
Страница 174: ......
Страница 175: ...D List of Illustrations and Tables...