Chapter 2. Technical Data
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
2-4
2.2.8
Trip and Close Outputs
2 contacts normally open, one of which is configurable internally to closed.
I DC Maximum Limit (with resistive load)
30 A
in
1 s
I DC Continuous Service (with resistive load)
8 A
Close
2500 W
Breaking Capability (with resistive load)
150 W
- max. 8 A - (48 Vdc)
55 W
(80 Vdc - 250 Vdc)
1250 VA
Break (L/R = 0.04 s)
60 W
at 125 Vdc
Switching Voltage
250 Vdc
Momentary Close Time Trip Contacts remain Closed
100 ms
2.2.9
Auxiliary Contact Outputs
Electrically separate open and closed contacts and normally open contacts.
I DC Maximum Limit (with resistive load)
5 A
in
30 s
I DC Continuous Service (with resistive load)
3 A
Close
2000 W
Breaking Capability (with resistive load)
75 W
- max. 3 A - (48 Vdc)
40 W
(80 Vdc - 250 Vdc)
1000 VA
Break (L/R = 0.04 s)
20 W
at 125 Vdc
Switching Voltage
250 Vdc