Annex B. DNP 3.0 Communications Protocol
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
B-4
Echo Control
The activation or deactivation of the transmission echo
Note: warning time and echo control settings are used to have various equipments connected to a concentrator
type CCY and working in multi-master mode.
Metering Changes (Deadband Values)
16 analog metering bands (from 0 to 15) can be set. The setting represents the percentage over
the maximum value of the measure that will be taken as reference to test if there is an
analogical change to record. In other word, a change will be recorded if the difference in the
analogical measures is greater than the set percentage.
If it is adjusted to 100%, analogical changes in this measure will not be recorded which is then
understood as being in a deactivated state.