Chapter 5. Settings
5-9
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
5.2
Control Subsystem Settings
5.2.1
Configuration Settings
Passwords
The default Password which enables access to every terminal unit setting is 2140. The user may modify
the passwords via the keyboard for the following actions:
Password 1: Configuration
Password 2: Settings
Local Port Communications
Setting
Range
Terminal Address
Not sensitive - enter any
number
Baud Rate
4800 Bauds
Stop Bits
1
Frontal Port Parity
0 (no parity) - 1 (even parity)
Remote Port Communications
Setting
Range
Step
Terminal Address
0 - 254
1
Baud Rate
300 - 19200 Bauds
Stop Bits
1 - 2
Parity
0 (no parity) - 1 (even parity)
Communications Timeout
0 - 100 ms
1
Rated Frequency
50 Hz / 60 Hz
Date and Time
Keyboard updating
5.2.2
General Settings
General Settings
Setting
Range
Step
CT Ratio
1 - 3000
1
VT Ratio
1 - 3000
1
Transducers (*)
Constant
0.00 to 99999.99
Quantity
kw, kVAr, A, kV
Type
2.5; 0.5;
1.0; 0-1 mA
(*)The transducer output type depending on the model.
Содержание 7IRD-A
Страница 2: ......
Страница 164: ......
Страница 165: ......
Страница 166: ......
Страница 167: ......
Страница 168: ......
Страница 169: ......
Страница 170: ......
Страница 171: ......
Страница 172: ......
Страница 173: ......
Страница 174: ......
Страница 175: ...D List of Illustrations and Tables...