12
ZP1-F Series Operation Manual
Tests
A zone test is indicated as follows:
• General Test LED: On steady.
• Corresponding Zone LED: On steady yellow.
• Control panel buzzer: Off.
A sounder test (or evacuation test for NBN S 21-100) is indicated as follows:
• General Test LED: On steady.
• Sounder LED: On steady yellow.
• Control panel buzzer: Off.
A fire routing test (or warning test for NBN S 21-100) is indicated as follows:
• General Test LED: On steady.
• Fire Routing On/Ack LED: On steady yellow.
• Control panel buzzer: Off.
A fire protection test is indicated as follows (NEN 2535 only):
• General Test LED: On steady.
• Fire Protection LED: On steady yellow.
• Control panel buzzer: Off.
Out of service
The control panel is out of service when there is insufficient or no mains or
battery power. Zone and input detection does not operate, but the rest of the
system is operational. In this state, the control panel may receive network events
which activate its outputs.
Out of service is indicated as follows:
• Out of Service LED: On steady.
• Supply Fault LED: Flashing if there is no mains power and the battery voltage
is insufficient. On steady if the mains power is insufficient and no battery
power is detected.
• Control panel buzzer: Sounding intermittent.
When power is re-established the control panel returns to its former status.
Note:
When the control panel indicates
out of service,
your fire alarm system is
partly inactive and your site is not properly protected. Contact your installation or
maintenance contractor immediately to investigate the problem.