ZP1-F Series Operation Manual
Enabling or disabling a configured fire routing delay (or warning delay for
NBN S 21-100)
To enable a configured fire routing delay (or warning delay for NBN S 21-100),
press the Fire Routing Delay button (or the Warning Delay button for
NBN S 21-100). To disable the delay, press the button again.
Note:
Availability of this feature is subject to configuration and its functionality
may vary for each zone. Contact your fire system installation or maintenance
contractor to confirm your configuration details.
Enabling or disabling a configured extended fire routing delay
If configured, the extended fire routing delay is enabled or disabled at the same
time as the standard fire routing delay.
In NEN 2535 operating mode, the extended fire routing delay becomes the active
delay when sounders are stopped (by pressing the Sounder Start/Stop button)
and remain stopped when the standard fire routing delay time has elapsed.
In EN 54-2 Scandinavia operating modes, the extended fire routing delay
becomes the active delay when an extended fire routing delay switch is activated
while the standard fire routing delay elapses. (This delay option is also available
for EN 54-2 and NEN 2535 operating modes if configured during installation.
Contact your fire system installation or maintenance contractor to confirm your
configuration details.)
Testing a zone
To test a zone, press the General Test button, and then press the corresponding
zone button. The maximum number of zones that may be tested at the same
time is four.
A zone in test is indicated as follows:
• General Test LED: On steady.
• Zone LED: On steady yellow.
When an alarm is activated in a zone in test:
• Zone alarm LEDs are steady or flashing, depending on the source of the
alarm.
• Fire routing and other zone-dependent functions are not activated.
• Unless configured otherwise, the sounders are activated for 5 seconds and
the Sounder Start/Stop LED is steady (optional).
• Unless configured otherwise, the control panel buzzer sounds continuously
(see note).
• The control panel will reset automatically after 5 seconds and clear alarms for
the zone in test.
To end the test, press the Test button, and then press the Zone button again.
If there is a fire alarm in another zone not in test, the control panel responds to
the alarm event as configured.