ZP1-F Series Operation Manual
9
Audible indicators
The control panel buzzer acts as an audible indicator to highlight system events.
It can sound a continuous tone or an intermittent tone.
Table 6: Audible indications
Indication
Description
The control panel buzzer sounds
continuously
Indicates a fire alarm or a system fault
The control panel buzzer sounds
intermittently
Indicates all other faults
Summary of status indications
This section includes a summary of the default control panel status indications.
Standby (normal status)
Standby, or normal status, is indicated as follows:
• Supply LED: On steady.
• Sounder or Evacuation Delay LED: On steady if a sounder or evacuation
delay was enabled.
• Fire Routing or Warning Delay LED: On steady if a fire routing or warning
delay was enabled.
• Control panel buzzer: Off.
Fire alarm
Fire alarm status is indicated as follows:
• General Fire Alarm LEDs: Flashing if the alarm was activated by a detector.
Steady if the alarm was activated by a manual call point.
• Zone LED: Flashing red if the alarm was activated by a detector. Steady red if
the alarm was activated by a manual call point. Shows which zones are in
alarm.
• Sounder Delay LED: On steady if a sounder delay was enabled. Flashing
while the delay is active (counting down). On steady when the sounders are
active (sounding).
• Fire Routing Delay LED: Flashing slow when a fire routing delay is active
(counting). Flashing fast when an extended fire routing delay is active
(counting).
• Fire Routing ON/ACKd LED: Flashing when fire routing is activated. On
steady when the fire routing signal has been acknowledged by the remote
monitoring equipment.
• Control panel buzzer: Sounding continuous.