OPERATION
ZIPPER MASCHINEN GmbH www.Zipper-Maschinen.at
33
ZI-STE1800IV
5.
Move the tank cap vent lever to the "OFF" position.
18.5.3
Stopping the machine in an emergency
1.
In case of emergency, switch the fuel tap to the “OFF”
position.
NOTICE:
Avoid stopping the machine this way in non-
emergency situations, as this poses a risk of causing
damage to the engine.
18.5.4
Run light and overload indicator light
1.
While the machine is running under normal operating
conditions, the green run light (1) is on.
2.
If the machine is overloaded or a short circuit occurs in
a connected device, the green output indicator light
switches off.
3.
Instead, the red overload indicator light (2) turns on.
The current that feeds the connected devices is
interrupted at that time.
4.
Disconnect the connected devices from the machine.
5.
Stop the machine.
6.
Check the power specifications of the connected
devices.
7.
Wait 2 minutes.
8.
Start the machine again.
9.
When the red overload indicator light (2) goes out and
the green run light (1) lights up again, you can
reconnect the electrical devices.
10.
Otherwise, it is recommended to turn off the machine
and check the problem.
18.5.5
Oil level indicator light
1.
Low engine oil level while the machine is running:
The yellow oil level indicator light lights up.
The engine is switched off automatically after 10
seconds to prevent any engine damages caused by
an insufficient quantity of oil.
Refill engine oil to a sufficient level. Proceed as
described above.
The yellow oil level indicator light goes out and the
machine can now be started again.
2.
Low engine oil level at the time of switching off the
machine:
The engine does not start.
The yellow oil level indicator light lights up during
the starting process (pulling the recoil starter
handle).
Refill engine oil to a sufficient level.