9.10.2.4
Limit ON / OFF, Function
|
3D
|
The value for
“
Limit
”
adjusted in the Controller Setup, is activated over a digital input.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
For
“
D1
”
Inverting
“
OFF
”
, limitation active at closed contact.
Controller
24V
D1 D1
1
0
n = 0- 80 %
1
0
- - - - -
n = 0- 100 %
10.05.2007
v_3d_limit.vsd
1
1
Setting
“
Limit
”
(depending on device type in: %, Hz, rpm)
9.10.2.5
Switch over Input signal
“
E1
”
/
“
E2
”
, Function
|
4D
|
Switch over between Input signal 1 (Analog In 1 terminal
“
E1
”
) and input signal 2 (Analog In 2 terminal
“
E2
”
).
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
24V
D1 D1
1
0
n = 0- 100 %
0
1
Si 1
Si 2
E1
GND
E2
GND
Si 1
Si 2
26.05.2010
v_4d_umschaltung_e1_e2.vsd
Controller
Si 1
Signal 1
Si 2
Signal 2
For mode speed controller (
1.01
) Base setup for
“
E2 Analog In
”
:
|
1E
|
necessary.
9.10.2.6
Set 1/2 or Setpoint 1/2, Function
|
5D
|
Switch over between
“
Set Intern1
”
and
“
Set Intern2
”
(for speed controller
1.01
)
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Controller
24V
D1 D1
1
0
n = 40 %
1
n = 80 %
0
- - - - -
- - - - -
11.05.2007
v_5d_vorgabe_intern_1_2.vsd
2
1
1
Setting
“
Set Intern1
”
(depending on device type in: %, Hz, rpm)
2
Setting
“
Set Intern2
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Set Intern1
”
at
opened contact /
“
Set Intern2
”
at closed
contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
Set Intern1
”
at
closed contact /
“
Set Intern2
”
at opened
contact.
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Programming
L-BAL-E079-GB 1706 Index 008
Part.-No.
52/87