9.2.6
For mode
2.03
Relay output for temperature monitoring
If the set value for the
“
minimum alarm
”
is not reached or the set value for the
“
maximum alarm
”
is
exceeded, a message is generated via the alarm symbol in the display. In addition,
„
Lmt E1 min
“
is
displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the
„
Maximum
alarm
“
. An external message follows via the factory-assigned
“
K1
”
relay. (IO Setup: K1 function =
|
2K
|
).
Alarm Minimum
Alarm Minimum
Setting range: OFF / -50...150.0
°
C
Factory setting: 0.0
°
C
Alarm Maximum
Alarm Maximum
Setting range: OFF / -26.9...150.0
°
C
Factory setting: 40.0
°
C
Lmt E1 min
Example for display if falling below setting
“
Alarm Minimum
”
alternating to the actual
value display.
Relay
“
K1
”
disengages (if not inverted).
Lmt E1 max.
Example for display if exceeding setting
“
Alarm Maximum
”
alternating to the actual
value display
Relay
“
K1
”
disengages (if not inverted).