9.1.2
Setting for operation
1.01
Setting
Setting
Set Internal1
Set Internal1
Setting range manual speed setting:
“
Min. Speed
”
-
“
Max. Speed
”
Factory setting: 50.0 Hz (
Setting
“
Max. Speed
”
)
Setpoint2
Setpoint2
Setting
“
Set Intern2
”
e.g. reduced value for night operation.
Switch over intern 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
Set external1
Set external1
“
ON
”
(factory setting) = speed setting by external Signal
“
OFF
”
= Setting
“
Set Intern1
”
Diagram setting signal and output frequency
F
out
[Hz]
08.05.2012
v_fxdm_setsig_min_max.vsd
1
2
3
4
5
6
7
8
9
10
Analog In 1
40
35
30
25
20
15
10
5
2
4
6
8
10
12
14
16
18
20
0...10 V
0...20 mA
10
20
30
40
50
60
70
80
90
100 0...100 % PWM
0
0
0
45
50
n-min OFF n-max. = 50 Hz
n-min 20 Hz n-max. = 45 Hz
n-min 10 Hz n-max. = 50 Hz
F
off
= 5 Hz
F
on
= 6 Hz
Fout:
Output frequency
Analog In:
Speed setting signal
n-min:
Min. Speed
n-max:
Max. Speed
Foff:
Shutdown Freq.
Fon:
Switch on Freq.
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Programming
L-BAL-E079-GB 1706 Index 008
Part.-No.
27/87