9.10.2.2
Enable ON/OFF function
|
1D
|
Remote ON/OFF (electronic disconnection) and Reset after a motor malfunction via
fl
oating contact.
The power section is electronically disconnected. Operation of the device is still possible after
pressing the
“
Esc
”
hotkey combination in switched-off condition. Signal- in and outputs remain active.
•
A programmed operating indicator relay (factory set
“
K1 function
”
=
|
1K
|
) reports the switch-off.
•
A programmed alarm relay (factory set
“
K2 function
”
=
|
2 K
|
) does not report the switch-off.
Display
STOP
for switch OFF
•
Controller
“
ON
”
for closed contact (fac-
tory setting).
•
Controller
“
OFF
”
with opened contact
When inverting in reverse i.e. equipment
“
OFF
”
with closed contact.
D1
D1
D1
D1
Digital IN 1
Digital IN 1
ON
OFF
10.05.2007
v_1d_freigabe_d1_d1.vsd
Contact at digital input e.g.
“
Digital In 1
”
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4
§
6)!
9.10.2.3
External fault Function
|
2D
|
Connecting an external alarm indication (via
fl
oating contact). The device continues to work un-
changed during an external indication to the digital input; the alarm symbol appears in the display.
This indication can be issued via the relay contacts (K1, K2) (
IO Setup function K1, K2).
Example for connecting an external alarm indication e.g. to digital input
“
Digital In 1
”
Controller
1~ S-ET..
3~ STDT..
TB
TB
TB
K1
D1
D1
10.05.2007
v_2d_externe_stoerung_set_stdt.vsd
1~ S-ET..
3~ STDT..
1~ S-ET..
3~ STDT..
•
Indication during closed contact (factory setting):
“
D1 Inverting
”
=
“
OFF
”
•
Indication during opened contact:
“
D1 Inverting
”
=
“
ON
”
Actual value
Alarm symbol for indication
“
External fault
”
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Programming
L-BAL-E079-GB 1706 Index 008
Part.-No.
51/87