7.3
External Setpoint / External speed setting in manual operation
External Setpoint or external manual operation is possible by 0 - 10 V (0 - 20 mA, 4 - 20 mA) signal at terminals
“
E2
”
and
“
GND
”
.
“
E2
”
con
fi
guration in base setup. For Potentiometer Analog Out1 (terminal
“
A1
”
) program to function
|
1A
|
=
“
+10 V
”
(like factory
setting
IO Setup). If a second sensor is connected at input 2 external Setpoint or speed setting in manual operation is
possible with additional modul
“
Z-Modul-B
”
(input E3
IO Setup / programming additional modul type Z-Modul-B).
E2 Analog In = factory setting 0 - 10 V
23.09.2011
v_extern_pot.vsd
0 - 10 V
0 - 10 V
10 k
A1
GND
E2
GND
External Setpoint
via external signal instead of
“
Setpoint 1
”
. The
“
external Setpoint
”
function must be activated in base setup
|
1E
|
for
“
E3 function
”
. The active external Setpoint value is displayed in the
“
info
”
menu group.
External speed setting
in manual operation. The
“
external manual operation
”
function must be activated in the basic settings
|
2E
|
for
“
E3 function
”
. Switchover between settings on the device and external manual operation via the digital input (
IO
Setup:
“
Control / manual operation
”
|
7D
|
).
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Base setup
L-BAL-E212-GB 1451 Index 003
Part.-No.
28/123