1
0
n = 0 - 100 %
04.04.2013
v_16d_umsch_sollw_plus_regelb_kreis2.vsd
Controller 2
n = 0 - 100 %
A2
A1
D1
24V
D1
Sensor 2
Controller 1
Sensor 1
16D
2.Setpoint1
Setting
“
2.Setpoint 1
”
= Setpoint 1 of control circuit 2
2.Pband1
Setting
“
2.Pband 2
”
= Pband 1 von control circuit 2
2.Setpoint2
Setting
“
2.Setpoint 2
”
= Setpoint 2 of control circuit 2
2.Pband2
Setting
“
2.Pband 2
”
= Pband 2 von control circuit 2
Info
Operation with
“
2.Setpoint2
”
and
“
2.Pband2
”
is signalized by the moon symbol for
reduced operation.
If Setpoint 2 was activated additionally for control circuit 1 or control circuit 2 by a digital
input with function
|
5D
|
/
|
9D
|
the moon symbol is already switched on.
If Setpoint 2 and Pband 2 was activated additionally for control circuit 1 by a digital
input with function
|
15D
|
, the moon symbol is already switched on.
28.7
°
C
E2 Actual
9.10.2.18
Timer function overwrite
|
21D
|
The timer output can be overwritten for a settable time with a selectable status if required (
timer).
To overwrite the timer function by pressing keys until the next timing change =>
“
Override Time
”
=
0 min.
The override time is activated by pressing a key at a digital input (example for D1 not inverted). The
bypass time can be ended prematurely by pressing another key.
If the contact remains closed, the override time also run out, then a short interruption is required to
reactivate.
24V
D1 D1
Limit ON: n = 0 - 80 %
Limit OFF: n = 0 - 100 %
11.09.2013
v_override_timer_3d_limit.vsd
Limit (3D)
Controller Setup
Override Timer
Contact depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
Example: speed limitation over Timer (Function
|
3D
|
)
The timer limits the maximum speed for a certain period of time (e.g. timer ON from 6:00 - 10:00 am).
With the
“
Override Timer
”
contact the limitation (from 6:00 - 10:00 am) activated by the timer can be
cancelled for an adjustable period
“
Override Time
”
(
timer / timer function overwritten: Override
Status = OFF)
To activate the limitation outside the programmed time (10:01 - 5:59 am) =>
“
Override Status
”
= ON
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
77/123