Setting
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
OFF
Min. Speed
Setting
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
50.0 Hz
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
50.0 Hz
Speed man.
Additional menu item for mode
4.02
and
4.03
with outside-temperature dependent target-
setpoint.
Outside-temperature dependent target-setpoint
AT
P-min.
-15 °C
T-min.
30 °C
T-Start
S1
18.09.2014
v_pressure_set_dep_outtemp.vsd
[Pa]
S2
T-Band
S1
Setpoint1
S2
Setpoint2
P-min.
Min. Setpoint
T-min
Min. temperature
T-Start
Setpoint reducing will start below this outside temperature
T-band
Temperature range
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
=
“
Analog In
2
”
) when being operated as a pressure regula-
tion device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active
“
Setpoint1
”
or
“
Setpoint2
”
is
automatically changed proportional to the
measured outside temperature (
Info:
“
Set-
point control
”
).
Setting
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
Setting range: 0.0..100.0 K
Factory setting: 30.0 K
30 K
T-Band SA
Setting
T-Start SA
Setpoint reducing will start below this outside temperature
Setting range: -10.0...40.0
°
C
Factory setting: 15.0
°
C
15
°
C
T-Start SA
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
47/123