9.3
Pressure control for condensers refrigeration
3.01
...
3.04
9.3.1
Base setup
3.01
...
3.04
Main menu
Base setup
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
Mode
Mode selection e.g.
3.01
3.01
Mode
Base setup
E1 Analog In
The sensor input is factory set for modes of group
3
to sensor type
“
MBG-30I
”
.
Measuring range: 0...30 bar
Output signal: 4 - 20 mA
Connection terminals:
“
E1
”
,
“
24V
”
Other settable sensors:
•
MBG-50I (measuring range 0...50 bar, output signal 4 - 20 mA)
•
DSF2-25 (measuring range 2...25 bar, output signal 4 - 20 mA)
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example 0 - 10 V sensor and measuring range 0 - 20 bar:
E1 Analog In = 0 - 10 V, E1 Unit = bar, E1 Decimals = 1, E1 Min. = 0,0 bar, E1 Max. =
20,0 bar
MBG0-30
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
0.00 bar
E1 Offset
Base setup
E1 Refrigerant
With
3.02
and
3.04
operating modes with input of the refrigerant, the device automati-
cally calculates the corresponding temperature for the measured pressure. The set-
tings for offset, target value and the controlling range are then carried out in
°
C or K.
Calculation for relative pressure (differential measurement of pressure relative to am-
bient pressure). No further settings are necessary for pressure sensors model e.g.
“
MBG-30I
”
or
“
MBG-50I
”
(measurement range 0 - 30 bar or 0 - 50 bar). In the case of
sensors with other measurement ranges, the
“
E1 Min. value
”
and the
“
E1 Max. Value
”
.
Setting in
“
bar
”
although unit display is in
“°
C
”
!
R503
E1 Refrigerant
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
41/123