Configuring Station Transponder Units
70
Figure 18: The Relay Menu
Figure 19: The Relay Parameter Selection Menu
The Parameter Selection Menu is used to select the way that the relay is reset (deactivated)
after it has been activated. It also provides a way to manually operate the relay for test
purposes. These reset conditions do not apply whenever a relay has been activated
manually by using the Relay Control input (see
following paragraphs give brief descriptions of the parameters shown in
.
Alert Off Reset
This selection causes the relay to reset once an alert is acknowledged, if the relay is also
configured to be activated by that alert’s on condition. Relays can be configured to
activate on the reception of an alert command, in the Alerts Menu.