SIMPLICITY INSTALLATION MANUAL.
Software:PANEL:R1107 & LOOP:R1062
Approved Document No: GLT.MAN-107
PAGE 30
Issue : 2.00 Authorised: GH Date: 4/06/2007
17. PCB TERMINATION CONNECTIONS.
LIVE NEUT- EARTH
RAL
MA
IN
S F
US
E
3A
HB
C CE
RA
M
IC
CONN29
FS1 FS2
FS3
1 2 3 4 5 6
7 8 9
10
LOOP WIRING
FLT REP
CLASS
CHANGE
A-
A+
B-
B+
+
+
+
+
+
11
12
13
17.1 CONNECTIONS
Connection No
Description
Use
1
LOOP 1A +&-
Connect to loop 1 side A
2
LOOP 1B +&-
Connect to loop 1 side B
3
FIRE REPEAT OUTPUT
24V on fire (including test mode). Use to drive relay.
4
FAULT REPEAT OUTPUT
Normally powered. 0V on fault. Use to drive FLT relay.
5
CLASS CHANGE
Join terminals to activate sounders
6
AUX SUP +&-
24 volt supply. 100mA Max
7
B & -
Connect 2 x 12V SLA batteries in SERIES (ie 24V)
8
THERMISTOR
Thermistor to prevent thermal overcharge
9
AC AC
Connected to transformer secondary (30VAC)
10
CONN 27
EARTH connection to display PCB & SCREEN TAG
11
CONN 3
50 way ribbon cable to display PCB
12
CONN 29
Filtered mains to transformer
13
CONN 6
MAINS TERMINAL BLOCK
17.2 FUSES
FUSE NO
DESCRIPTION
RATING
FS1
Charger Fuse
1.6A time delay 5 x 20mm glass
FS2
Battery Fuse
1.6A time delay 5 x 20mm glass
FS3
Aux Supply
100mA time delay 5 x 20mm glass
INLET FUSE
Mains Protection Fuse
2.0A Quick Blow HBC 5 x 20mm ceramic