EDA-C5000 Installation Manual 

 

Ref:EDA_C5000_install_V104 

 

Electro-Detectors

 

Zerio Plus 

 

EDA-C5000 Radio Callpoint Installation Manual 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The EDA-C5000 Radio Callpoint is used as part of the Zerio Plus Radio Fire Alarm System.  It cannot be 
used with other ranges of Electro-Detectors products. 
 

 
To fix the unit to the wall 

The  call  point  should  be  fitted  in  an  appropriate  position  as  detailed  in  BS5839  Part  1.  Care  should  be 
taken to try and reduce the possibility of the unit been accidentally knocked or being obscured from view. 
The  back  box  should  be  separated  from  the  unit  by  removing  the  screw  on  the  underside  and  pulling 
apart.  The  back  box  should  be  screwed  to  a  flat  surface  using  2  x  No  8  (4mm)  screws  of  appropriate 
length for the material that the unit is being mounted on. It is recommended that the back box should be 
used as a template for the screw holes. If the surface is not flat, the unit may buckle when screwed tightly 
to the surface. It is recommended that the units not be secured too tightly or a mounting plate be fixed to 
the  wall  first.  The  unit  should  be  fitted  away  from  any  metal  objects  and  a  radio  survey  for  the  position 
should have been carried out prior to installation. 
 
Before the unit will operate on a system, it must be programmed via the control panel.  To program the 
unit  the  panel  must  be  set  in  the  appropriate  mode  to  add  a  device  to  the  system.    Please  refer  to  the 
panel manual for further information.  Before adding the device to the system you will need to determine 
what  unit  number/address  the  unit  is  to  be  programmed  to.    The  zone  number  and  text  location 
information should also be to hand but this can be added/changed later. 
 

To put the callpoint into log mode, follow the procedure below:- 

 

1.

 

Remove the back box by removing the screw on the bottom of the unit. 

2.

 

Ensure the power jumper is removed. 

3.

 

Press and hold the unit removal and the log-on button simultaneously. 

4.

 

With these buttons pressed down, fit the power link. 

5.

 

Hold the buttons down until three rapid beeps are heard. If the mode is successfully selected the 
LED on the front of the unit will glow green. 

6.

 

Both buttons can now be released. 

7.

 

Follow the instructions inside the panel manual to add the device to the system. 

 

       

  

 

0359 

 

Electro Detectors Ltd. 

Electro House 

Edinburgh Way 

Harlow, Essex 

CM20 2EG, UK

 

EN54-11:2001 
EN54-25:2008 
 
0359-CPR-00232 (2013) 
DOP-EDA-C5000 
 
 

EDA-C5000

 (type A) 

Radio manual call points 
for fire detection and fire 
alarm systems for 
buildings 