background image

 

EDA-C5000 Installation Manual 

 

Ref:EDA_C5000_install_V104 

 

Electro-Detectors

 

Breaking  the  glass  will  cause  the  panel  to  indicate a fire condition and, if programmed, will operate any 
sounders on the system.  The unit is also fitted with a test facility so that the system can be tested without 
the glass being broken.  To operate the test facility, the special key supplied with the callpoint should be 
inserted into the unit on the bottom face in the centre.  This will cause the plastic front and glass to drop 
allowing the unit to transmit an alarm condition.  The LED will illuminate red and a low level beeping will 
be  emitted  from  the  unit.  The  beeping  will  cease  once the glass is replaced or the test key  is removed, 
however the LED will remain illuminated until the panel is reset. 
 

 
To change the battery in the callpoint:- replacement part: 1 x EDA-Q690 

 

The battery should last approximately  5 years in the callpoint. Always use batteries supplied by Electro Detectors 
otherwise this will invalidate the certification. Many similar battery technologies are available but only the ones that 
meet certain properties can be used with these units. The battery pack is fitted with 2xAA Lithium Thynol Chloride 
cells.  Min  voltage  3.0V,  Max  3.7V.  When  the  battery  is  approaching  its  end  of  life  the  unit  will  transmit  a  low 
battery condition, which will be indicated on the control panel.  The system will still function for at least a further 
60 days in this condition before the unit fails to work.  Once the batteries are too flat to operate, the unit will either 

indicate a “verify fail” fault, because the panel has lost communication with the device, or a battery fault will be 

displayed.  Should either of these be witnessed, the batteries should be changed immediately.  If the unit detects a 

fault with the battery a ‘battery fault’ will be indicated on the panel.  

 

 
1.

 

Remove the back box. 

2.

 

Remove the power link. 

3.

 

Remove the old battery pack. 

4.

 

Fit the new battery pack making sure t

he battery’s pins are lined up and pressed down.

 

5.

 

Press and hold the unit removal and log-on button simultaneously. 

6.

 

With these buttons pressed down, fit the power link. 

7.

 

Let the unit go into its log-on mode (ie three rapid beeps) and keep the buttons pressed down. 

8.

 

After a further five seconds a series of beeps will sound, at this point release the buttons.  This will 
re-set the battery counter. 

9.

 

Refit the device onto its back box. 

 

Faults displayed on the control panel from callpoints:- 

 

Low Battery: 

The batteries are approaching their end of life.  The unit will continue to operate for a 

further 60 days before the batteries need to be changed. 
 

Verify Fail: 

The panel has lost communication with the device, this could be caused by the batteries 

being  flat,  the  unit  failing  to  operate,  something  obstructing  the  radio  signal  path  or  the  device  not 
being installed correctly with an adequate signal strength. 
 

Battery Fault:

 The unit has detected a problem with the battery. 

 

Unit Removal: 

If the unit is removed from its back box, the panel will display a unit removal/tamper 

fault. 
 
 

Отзывы: