SIMPLICITY PLUS INSTALLATION MANUAL.
Software Version :PANEL-R1578 & LOOP-R1062
Approved Document No: GLT.MAN-107
PAGE 7
Issue : 2.00 Authorised: GH Date: 4/06/2007
5. MOUNTING THE FIRE ALARM PANEL
The Simplicity comes with many cable entry holes. If another entry hole is required, it is strongly recommended
that the panels door be removed to avoid accidental damage. Also, the termination PCB should be removed and
stored in a safe place. This would also help while fixing the back box to the wall.
5.1 PLANNING CABLE ENTRY
Fig.2 below shows the location of the cable entries to facilitate planning of wiring (home runs) to be brought to
the panel.
The grommets can be easily removed by a push from inside the control panel box.
If a grommet is removed, fill the hole with a brass cable gland. If any knockout is removed, but subsequently not
used, it should be covered up.
The 230Va.c. Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of
the back box. (Refer to “Connecting the Mains” on Page 8).
5.2 FIXING THE BACK BOX TO THE WALL
Figure 2: Plan view inside the enclosure without PCBs. Side view for surface installation.
Wall Mount
Flush Mount
12 x 19mm grommet cable entries
2 x 19mm
knock-out
cable entries
355mm
275mm
250mm
195mm
60 x 20mm
back cable
entry
60 x 20mm
back cable
entry
73mm
Fix the enclosure to the wall using the three mounting holes provided.
Check the build & condition of the wall to decide a suitable screw fixing.
The mounting holes are designed for No 8 roundhead or countersunk woodscrews (or similar).
Remove any debris from the enclosure.
Take care not to damage the FACP during installation.