SIMPLICITY INSTALLATION MANUAL.
Software:PANEL:R1107 & LOOP:R1062
Approved Document No: GLT.MAN-107
PAGE 24
Issue : 2.00 Authorised: GH Date: 4/06/2007
14. TEST MODE
14.1 WHY USE TEST MODE
To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is available.
When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for
approximately eight seconds on and four seconds off. This cycle continues until the cause of the Alarm is
removed (either by the test smoke clearing from the detector or the manual call point being reset), sounders will
then stop activating.
Should an Alarm occur on a zone that is not programmed to test, the Fire Alarm Panel will cancel the test mode.
After the cause of the alarm has been checked, and the panel reset, test mode will have to be selected again to
resume testing.
14.2 TO PROGRAMME ZONE IN TEST MODE
NOTE: Only
one zone
can be programmed in test at any one time.
1. Insert and turn control key to enabled position;
2. Press TEST Button. The screen will prompt for the test code
3. Enter the Test code
2 4 8.
4. The screen will now show Test Mode.
5. Press TEST FUNCTION SELECT button to select the zone to be
tested.
6. Press CONFIRM to enter test mode for this zone
The General Test and Zone Test LEDs will now be lit.
7. Detectors in this zone can now be tested with smoke spray. The
sounders will operate for about 4 seconds, then they will reset. This
cycle will continue until all smoke spray has cleared from the detector.
8. Once testing of that zone is completed, press TEST FUNCTION SELECT button to move to another Zone or
turn the control key switch to off position to exit test mode.
14.3 TO PROGRAM SOUNDER CIRCUITS IN TEST MODE
NOTE: Only the ADDRESSABLE SOUNDERS can be tested with the loop sounder one man test mode.
The ASSOCIATED SOUNDER BASES cannot be tested this way because of their slower stop/start time.
1. Insert and turn control key to enabled position;
2. Press TEST Button, The screen will prompt for the test code.
Enter the code 2 4 8.
3. The screen will now show Test Mode, Zone 1, Normal Operation.
4. Press TEST FUNCTION SELECT button to select the sounder
to be tested.
5. Press confirm to enter test mode for this function. The LED will
now be on steady.
6. The Sounders will now pulse 3 seconds on, 3 seconds off until
they are taken out of test mode. This allows all the sounders
to be tested for correct operation, and dB output.
7. Once testing of that sounder circuit is completed, press
TEST FUNCTION SELECT button to move to another circuit, or
turn the control key switch to off position to exit test mode
To test associated sounder bases, use the stop/start sounder button (evacuate). Note that the sounders will take
up to 9 seconds to start.
***NOTE***Associated sounder bases are controlled by the detector.
Removing the detector will leave the
sounder base inoperative.
Test Mode
Zone 1
Normal Operation
Enter Access Code
█
Test Mode
Zone 2
Test Active
Test Mode
Zone 1
Normal Operation
Enter Access Code
█
Test Mode
Loop Sounders
Test Active