16. STANDBY BATTERY REQUIREMENTS
The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Simplicity Fire Alarm
System
Device Product
Code
I
q
(mA)
I
flt
(mA)
I
alm
(mA)
Max
per
Loop
Max
per
System
SIMPLICITY 64 Fire Alarm Panel
SP-64
100
150
200
N/A
1
SIMPLICITY 126 Fire Alarm Panel
SP-126
100
150
200
N/A
1
Premier Addressable REPEATER PANEL REP-AD
200
220 220 N/A 4*
Fyreye Addressable Ionisation Smoke Detector FEAI2000
0.6
N/A
2
126
126
Fyreye Addressable Optical Smoke Detector FEAO2000
0.6
N/A
2
126
126
Fyreye Addressable Heat Detector FEAH2000
0.6
N/A
2
126
126
Fyreye Addressable High Temperature Heat Detector
FEAHH2000
0.6
N/A
2
126
126
Fyreye Addressable Multi-point Detector FEAOH2000
0.6
N/A
2
126
126
Fyreye Addressable Sounder Base
FEA-SB
0
N/a
10
32
32
Zeta Addressable Call Point (EN54)
ZT-CP2/AD
0.5
N/a
3
126
126
Zeta Addressable Call Point
ZT-MCP/AD
0.4
N/a
13
126
126
Zeta Weatherproof Addressable Call Point
ZT-
MCP/AD/WP
0.4 N/a 13 126 126
Zeta Input Unit
ZIU
2
2
2.5
126
126
Zeta Input Output Unit
ZIOU
2
2
10
16
16
Zeta Sounder Control Module
ZSCC
2
2
10
16
16
Zone Monitor Unit
ZT-ZM
6
8-30
22
10
10
Fyreye Addressable Beam Detector (5-50m)
ZT-50RA
t.b.c. t.b.c. t.b.c. t.b.c. t.b.c.
Fyreye Addressable Beam Detector (50-100m)
ZT-100RA
t.b.c.
t.b.c.
t.b.c.
t.b.c.
t.b.c.
Zeta Addressable Maxitone Sounder
ZAMT
1.5
N/a
9
32
64
Zeta Addressable Miditone Sounder
ZAMD
1.5
N/a
9
32
64
Zeta Addressable Securetone Sounder
ZAST
1.5
N/a
9
32
64
Zeta Addressable Remote LED Indicator
ZTA/LE2
1.5
N/a
10
32
64
Conventional Sounders (via a sounder Control Circuit)
Zeta Conventional Maxitone Sounder
ZMT/8
0
N/a
15
N/a
N/a
Zeta Conventional Miditone Sounder
ZMD/8
0
N/a
15
N/a
N/a
Zeta Conventional Securetone Sounder
ZST/8
0
N/a
15
N/a
N/a
Zeta Conventional Megatone Sounder
ZIDC
0
N/a
200
N/a
N/a
Zeta Conventional Flasher
ZFL2RR
0
N/a
90
N/a
N/a
Zeta Conventional Sounder Flasher
ZLT/8RR
0
N/a
110
N/a
N/a
Zeta Conventional 6” Bells
ZTB6B/24
0
N/a
25
N/a
N/a
Zeta Conventional 8” Bells
ZTB8B
0
N/a
35
N/a
N/a
Conventional Detectors (via a Zone Monitor)
Fyreye Conventional Optical Detector FEO2000
0.06
N/a
25
N/a
N/a
Fyreye Conventional Heat Detector (A1R) FEHR2000
0.04
N/a
25
N/a
N/a
Fyreye Conventional Heat Detector (CS) FEFH2000
0.04
N/a
25
N/a
N/a
* The Simplicity can only power 1 repeater. Any subsequent ones will need a separate power supply.