background image

SIMPLICITY PLUS INSTALLATION MANUAL.  

 

 

Software Version  :PANEL-R1578 & LOOP-R1062 

 

Approved Document No: GLT.MAN-107

 

 

 

 

PAGE 6

 

Issue : 2.00         Authorised: GH      Date: 4/06/2007

 

4. FIRST FIX 
 
4.1 Mounting the Control Panel 
 

The control panel should be installed in accordance with the following recommendations:- 

 

The panel should be close to the main entrance of the building, so that it can be viewed by any fire-
fighting personnel entering the building. 

 

It should be fitted to a sturdy wall that will not flex unnecessarily.  

 

It should be mounted at eye level, in order for it to be viewed without need of a ladder. 

 

It should be installed in a dry, weatherproof place, preferably NOT in direct sunlight. 

 

It should be easily accessible, so that the responsible person can perform their regular fire alarm 
checks.  

 

4.2 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS 
 
All wiring must be installed to meet BS5839: Pt1: 2002 and BS 7671 (Wiring Regs) standards.  Other 
National standards of fire alarm system installation should be adhered to where applicable. 
 

Screened cables should be used throughout the installation to help shield the Panel from outside interference 
and ensure EMC compatibility. 
 
The two categories of cable according to BS5839: Pt1: 2002, Clause 26 “Fire Detection and Alarm Systems for 
Buildings (Code of Practice for System Design, Installation and Servicing)” are: 
 

Standard fire resisting cable – to PH30 classification of EN 50200 
Enhanced fire resisting cable – to PH120 classification of EN 50200 
(Note that all cables should be at least 1mm

2

 cross section 

 
On the Simplicity Panel the general recommendation would be to use standard fire resistant cable, such as GLT 
Exports Fire Defence Cable, Firetuff

 , FP200 or an equivalent. These cables are screened, and will provide 

good EMC shielding when properly grounded at the panel.  Certain system specifications may demand the use 
of a particular type of cable and due regard should be paid to this fact. 
 
Depending on the environment, the cables may need mechanical protection (such as a conduit). 
 

4.3 MAINS WIRING RECOMMENDATIONS 
 

The Mains supply to the FACP is fixed wiring, using 

Fire resisting

 3-core cable (Between 1 mm² and 2.5mm²) or 

a suitable 3-conductor system, fed from an isolating double pole switch fused spur, fused at 3A.

  IT SHOULD 

NOT BE CONNECTED THROUGH AN RCD.

 This should be secure from unauthorised operation and be 

marked ‘FIRE ALARM: DO NOT SWITCH OFF’.  The supply must be exclusive to the Fire Panel. 

MAKE SURE 

ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED

 

 
For information on how to connect Mains to the Panel’s Power Supply PCB, see page 8. 
Also refer to rating information on the mains cover inside the FACP. 
 

Содержание SP-64

Страница 1: ...INSTALLATION MANUAL Simplicity Plus 64 OR 126 DEVICE CAPACITY SINGLE LOOP ANALOGUE ADDRESABLE FIRE ALARM CONTROL PANEL...

Страница 2: ...15 8 2 ASSOCIATED SOUNDER BASES 15 8 3 SUPPORTED SOUNDER TYPES THEIR APPLICATIONS 15 9 AUXILIARY INPUTS OUTPUTS 15 9 1 AUXILIARY INPUT WIRING EXAMPLES 15 10 FIELD DEVICE TERMINATION 17 10 1 TERMINATIN...

Страница 3: ...accordance with our instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS...

Страница 4: ...STEM The table below lists the main advantages of addressable systems and how our panels use them FEATURE PREMIER AL PREMIER AD SIMPLICITY UNIQUE ALARM IDENTIFICATION PANEL LOOP ADDRESS LOOP ADDRESS L...

Страница 5: ...dentifies a call point alarm immediately Improved sounder base starting stopping time Option to disable individual points or whole zones Detector LED sounder can be operated from the menu to help iden...

Страница 6: ...s method of zone allocation is the maximum zone capacity of 16 devices If a zone has more than 16 devices it will need to be split into smaller zones Similarly a zone with only one device would leave...

Страница 7: ...Fire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resistin...

Страница 8: ...a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one...

Страница 9: ...zone cables to help minimise mains interference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock f...

Страница 10: ...er A maximum of 32 loop powered addressable sounders or sounder bases are permitted on the loop On the Simplicity Panel all Sounder Bases are always configured as common sounders Short circuit isolato...

Страница 11: ...UT L2 L 1 I O U T L1IN R C RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals are marked...

Страница 12: ...FEA RB Fyreye Addressable Relay Base 80 090 FE IB Fyreye Addressable Loop Isolator Base 80 100 FEA SB Fyreye Addressable Sounder Base 80 101 FEA SFB Fyreye Addressable Sounder Flasher Base 43 305 ZT...

Страница 13: ...e beyond the scope of this manual because of the distributed load of the sounders on the loop but the following table gives a rough guide for maximum cable lengths at various current loads for 3 diffe...

Страница 14: ...3 OFF 2 ON 1 OFF As an alternative to using this chart use the table on the following page SW 4 3 2 1 OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O 1111 LOOP 1 LOOP 2 SW...

Страница 15: ...off off on on on 46 on off off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off...

Страница 16: ...be more expensive Maximum 32 per loop for quick start stop Quiescent current high Uses device address Associated sounder base No Extra Cabling Doesn t occupy Device Address Can have more than 32 per l...

Страница 17: ...utput wiring Trigger I P FLT REP RELAY OUTPUT NO CM NC RELAY FAULT INDICATION DEVICE FIT BACK EMF DIODE ACROSS RELAY COIL Trigger I P RELAY OUTPUT NO CM NC RELAY AUTODIALLER FIT BACK EMF DIODE ACROSS...

Страница 18: ...CPU PCB SERIAL REPEATER COM TERMINATION PCB AUX SUP 28V TERMINATION PCB AUX SUP 0V 11 2 SERIAL PRINTER CONNECTION The Simplicity has a connection for a serial printer The printer will print out panel...

Страница 19: ...er Loop 1 only and the total number of devices on that loop Check that the number of devices seen compares to the number expected If it is different refer to the fault finding guide 8 The panel is now...

Страница 20: ...atus Select a detector that does NOT have a sounder base attached 2 Press the Disablement SELECT button The sounder symbol turns off to show that this detector no longer has an associated sounder Pres...

Страница 21: ...issing The device is not communicating ie removed damaged or Address setting changed Side A Only There is a break in the cable and the device is only seen from Side A Side B Only There is a break in t...

Страница 22: ...e Keyswitch ON Keyswitch OFF Sounders Silenced Configure Loops Time Date Set Zone Disabled Zone Enabled Device Disabled Device Enabled Zone Test Start and Zone Test Finish Note during installation and...

Страница 23: ...ctive To disable the call points as well disable them individually as points see 13 3 4 If more than one zone or sounder needs to be disabled then press DISABLEMENT SELECT again until the required zon...

Страница 24: ...enable several disabled points is to disable the zone then re enable it To view from the Device Status screen press enter then option 2 to select Device Status If a device is enabled the screen will...

Страница 25: ...n they will reset This cycle will continue until all smoke spray has cleared from the detector 8 Once testing of that zone is completed press TEST FUNCTION SELECT button to move to another Zone or tur...

Страница 26: ...ip switch setting 4 If this does not cure all double addresses go to the known location and temporarily remove the device The panel will now report the type of device that was also configured to this...

Страница 27: ...if it is a Positive or Negative voltage shorting to earth Earth Fault Pos or Earth Fault Neg DO NOT DISCONNECT THE MAINS EARTH CONNECTION THIS WILL CAUSE A PROBLEM WITH THE PANELS OPERATION 15 6 DOUB...

Страница 28: ...e B If both loop LEDs are off then this indicates that there is a short on the loop that the isolators couldn t bypass Check that the isolators are enabled and aren t set for a cable continuity check...

Страница 29: ...26 126 Zeta Input Output Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 6 8 30 22 10 10 Fyreye Addressable Beam Detector 5 50m ZT 50RA t b c t b c t b c t...

Страница 30: ...detector 0 00005 Amp 50 A Optical Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 30 Sounder bases and the required standby is 24 hours It will need to...

Страница 31: ...Normally powered 0V on fault Use to drive FLT relay 5 CLASS CHANGE Join terminals to activate sounders 6 AUX SUP 24 volt supply 100mA Max 7 BATTERY Connect 2 x 12V SLA batteries in SERIES ie 24V 8 TH...

Страница 32: ...8 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours LOOP VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS LOOP POWERED SOUNDERS ONLY AUXILIARY FAULT OUTPUT 24V RELAY D...

Отзывы: