SIMPLICITY INSTALLATION MANUAL.
Software:PANEL:R1107 & LOOP:R1062
Approved Document No: GLT.MAN-107
PAGE 17
Issue : 2.00 Authorised: GH Date: 4/06/2007
10. FIELD DEVICE TERMINATION
10.1 TERMINATING THE WIRING.
LIVE NEUT- EARTH
RAL
INLET MAINS
SUPPLY
INTERNAL
WIRING
Brass Glands
LIVE NEUT- EARTH
RAL
CONN29
FS1 FS2
FS3
1 2 3 4 5 6
7 8 9
10
LOOP WIRING
FLT REP
CLASS
CH ANGE
A- A+
B- B+
+
+
+
+
+
11
12
13
MA
IN
S F
US
E
2A
H
BC
C
ER
AM
IC
CONN5
Figure 6: Detector and Sounder Circuit Connection
11 OTHER CONNECTIONS
11.1 REPEATER CONNECTION
The Simplicity has an RS485 connection for a serial repeater. The repeaters are display only (no control). A
single repeater can be powered from the panel`s Auxiliary Supply. If 2 or more are to be connected, then they
must be powered from external 24V power supplies. The panel supports up to 4 repeaters.
Connections
Simplicity Plus
Addressable Repeater
CPU PCB:SERIAL RE
COM +
CPU PCB:SERIAL REPEATER -
COM -
TERMINATION PCB:AUX SUP +
+28V
TERMINATION PCB:AUX SUP -
0V
11.2 SERIAL PRINTER CONNECTION
The Simplicity has a connection for a serial printer. The printer will print out panel events as they occur. The
recommended printer is an Epson LQ300 II+. The serial port on the Simplicity is configured to this printer`s
default settings.
Connections
Serial
Port
Settings
Simplicity
25 pin D connector
Setting
Value
TX
Pin 3 (RX)
Baud Rate
19200
RX
Pin 2 (TX)
Data Bits
8
GND
Pin 7 (GND)
Stop bits
1
CTS
Pin 4 (RTS)
Parity
NO
DSR
Pin 20 (DTR)
Flow Control
Hardware
MAKE SURE ANY SPARE
ENTRY HOLES ARE
COVERED WITH THE
GROMMETS PROVIDED
All cables entering the enclosure
should have brass cable glands,
which will ensure a good ground to
the steel EMC cable grounding plate.
The Detector and Sounder circuits
should be connected to the
appropriate connector block on the
Termination PCB as shown in Figure
6 below.
All screens should be terminated at
the brass earthing strip as shown in
Figure 6
(For detailed detector and alarm
circuit wiring diagrams, please refer
to pages 4 and 5.)