On/Off
[
No Change
/ Off / On
], if “No Change” is selected, the machine will
keep the last state it was in before the scene reception.
•
Mode
[
No Change
/ Heating / Cooling / Fan / Dry
].
Note
:
if fan mode is selected, setpoint temperature and automatic fan speed
cannot be selected
.
•
Flaps
[
No Change
/ Swing / 1 / 2 / 3 / 4 / 5
]. This option only will be visible in
case of having enabled Flaps
; on the contrary this section will appear as “Not
Available
”
•
Speed
[
No Change
/ Automatic / 1 / 2 / 3 / 4 / 5
].
•
Setpoint
[
disabled
/enabled
]:
➢
Value:
•
“
No Change
”. Only available if “Setpoint” parameter remains disabled.
•
“
10…
25
…32
”.
Note
:
this setpoint value may be modified by the setpoint limits during runtime.
2.4.4
ERROR HANDLING
KLIC-PA is capable of managing two error types:
•
Internal errors:
errors in the communication process between KLIC-PA and
the A/C unit:
➢
Communication error
: KLIC-PA received no response of the A/C unit
during 2 minutes.
A notification led is available, so the LED of the device will shine in green
when no response error is activated, and will turn off when this error
disappears.
➢
No response
(time out)
: After KLIC-PA has stablished communication with
the A/C unit and the configuration has been done, no response has been
received by the A/C unit during a time.