When operating time object reaches its maximum value, it will be send through KNX bus
(in spite of the fact that the periodical sending has not been configured) and it will keep
this value until the user reset it.
AUTOMATIC OFF
Figure 14. A/C Gateway. Configuration. Automatic off.
•
Automatic Off
[
disabled
/enabled
]:
enables the
“
[AC] Automatic Off
” and
“
[AC] Automatic Off (Status)
” binary object, which allow the A/C unit to be
switch-off or the current status to be read, respectively. A/C unit by sending it
a value of “1” and a later switch-on by sending it a value of “0”. This object will
be typically linked to a window sensor or a similar event trigger. Automatic off
will be also active if the unit is previously in off state, so, the unit will not be able
of being on until this situation finishes.
During the temporary switch-off state, KLIC-PA will still monitor any control
orders being received (setpoint, fan speed, etc.), so they can be applied once
it leaves such state.
➢
Automatic Off Object Polarity
[
0 = Activate; 1 = Deactivate /
0 =
Deactivate; 1 = Activate
]: sets the polarity of the above object.
➢
Automatic Off Delay
[
0…
30
…3600
][
s
]: sets the time waits before switching
the AC machine off. Any switch-off order received during the delay will abort
the time count. This delay can be modified at runtime through the object
“[AC] Automatic Off Delay”
. The sending of the value “0” disables the
automatic off functionality.
Note
:
switch-on orders sent to the
A/C
unit from a wireless control, have a
higher priority than the Auto Off mode.