KLIC-PA
Technical Support:
19
•
“[AC] Temperature Setpoint: Upper Limit (Status)”
: 2-Byte object with the
upper limit current value.
Notes
:
•
These parameters only can be set as integer values in ETS. However, at run
time the associated objects allow decimal values.
•
The A/C unit set a fixed temperature setpoint in Fan and Dry mode, this is the
reason why KLIC-DD v3 will not send the setpoint value to A/C unit, however
the value will be saved to send when leaving these modes.
REFERENCE TEMPERATURE
Figure 11. A/C Gateway. Configuration. Reference temperature.
It is available by default the object
“[AC] Reference Temperature (Status)
”, which
informs the temperature that the A/C Unit use as reference to do the temperature control.
In addition, is possible to configure the next option:
•
External Reference Temperature Object
[
disabled
/enabled
]: enables a 2-
Byte object “
[AC] External Reference Temperature
” which will receive the
temperature values provided by an external temperature probe and these
values will be employed by the A/C unit to control the temperature (instead of
employing its internal values).
If during 3 minutes, no temperature values are received, values of the internal
probe will be recuperated again to execute temperature control, in the same
way as it will be controlled if KLIC-PA was configured disabling this option. If
a new external temperature value is received, the control will be again
executed by using this external value. The values allow to be received in this
object are include in [0-70] ºC (if different values are received, they will be
ignored).
FILTER