KLIC-DI VRV
http://www.zennio.com
Technical Support:
http://support.zennio.com
28
Number
Size
I/O
Flags
Data Type (DPT)
Implemented range
Name
Function
12
1 Bit
I
C T - W U
DPT_Switch
0/1
Heat Mode
1=Set Heat Mode;0=Nothing
13
1 Bit
I
C T - W U
DPT_Switch
0/1
Fan Mode
1=Set Fan Mode;0=Nothing
14
1 Bit
I
C T - W U
DPT_Switch
0/1
Dry Mode
1=Set Dry Mode;0=Nothing
15
1 Bit
I
C - - W U
DPT_Switch
0/1
Simplified Mode
0=Cool;1=Heat
16
1 Bit
O
C T R - -
DPT_Switch
0/1
Auto Mode (status)
1=Auto Mode Enabled;0=Disabled
17
1 Bit
O
C T R - -
DPT_Switch
0/1
Cool Mode (status)
1=Cool Mode Enabled;0=Disabled
18
1 Bit
O
C T R - -
DPT_Switch
0/1
Heat Mode (status)
1=Heat Mode Enabled;0=Disabled
19
1 Bit
O
C T R - -
DPT_Switch
0/1
Fan Mode (status)
1=Fan Mode Enabled;0=Disabled
20
1 Bit
O
C T R - -
DPT_Switch
0/1
Dry Mode (status)
1=Dry Mode Enabled;0=Disabled
21
1 Bit
I
C - - W U
DPT_Step
0/1
Fan [1bit]
0=Down;1=Up
22
1 Byte
I
C - - W U
DPT_Scene_Control
0-63
Scenes: Receive
Selected Scene Value
23
1 Bit
I/O
C T R W U
DPT_Switch
0/1
Setpoint Restriction
0=Disable;1=Enable
24
1 Bit
I
C - - W U
DPT_Switch
0/1
Auto-OFF
0=Disable;1=Enable
25
1 Bit
O
C T R - -
DPT_Switch
0/1
Internal Error: Communication
0=No Error; 1=Error
26
1 Bit
O
C T R - -
DPT_Switch
0/1
External Error
0=No Error; 1=Error
27
1 Byte
O
C T R - -
non-standardized
datapoint type
1-239
Type of External Error
Check Error's Table
28
2 Bytes
O
C T R - -
DPT_Value_Temp
0ºC
–
99ºC
Internal Temperature (status)
Temp. from internal sensor
29
2 Bytes
I
C - - W U
DPT_Value_Temp
0ºC
–
99ºC
Reference Temperature
Temp. from external sensor
30
1 Byte
I
C - - W U
DPT_Scaling
0% Posit. 1
1-20% Posit. 2
21-40% Posit. 3
41-60% Posit. 4
61-80% Posit. 5
81-100% In mot.
Swing [1byte]
0-80%=Fixed Pos.;100%=Mot.
31
1 Bit
O
C T R - -
DPT_Switch
0/1
Swing [1bit] (status)
0=Fixed Position; 1=Motion
32
1 Bit
O
C T R - -
DPT_Switch
0/1
Simplified Mode (status)
0=Cool; 1=Heat