KLIC-DI VRV
http://www.zennio.com
Technical Support:
http://support.zennio.com
21
Being the exterior unit in the
dry
or
fan
modes, if the KLIC-DI that controls the
slave of mode unit sends the
heat
mode then the slave of mode unit will switch
to
cool
mode.
Being the exterior unit in the
heat
mode, if the KLIC-DI that controls the slave of
mode unit sends the
cool
mode then the slave of mode unit will switch to
the
fan
mode.
Being the exterior unit in the
dry
or
fan
modes, if the KLIC-DI that controls the
slave of mode unit sends the
cool
mode, then the slave of mode unit will switch
to the
heat
mode.
Note: when KLIC-DI is configured as the master of mode, the wired remote controls of
the A/C unit cannot be used to set additional masters of mode.
3.2.7
SWING
Through this parameter, it is possible to select whether to permit controlling the swing
function (i.e., the slats that address the air flow) of the A/C machine. The availability of
such function in the particular A/C unit being controlled needs to be confirmed in
advance.
Important
:
in case of not being available swing control in the machine, enabling this
parameter may cause an abnormal behaviour of the air machine.
Figure 14
. Swing