ANNEX I. COMMUNICATION OBJECTS
“
Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular
meaning because of the specifications or restrictions from both the KNX standard or the application programme itself.
Number
Size
I/O
Flags
Data Type (DPT)
Implemented range
Name
Function
0
1 Bit
I
C - - W U
DPT_Switch
0/1
On/Off
Turn ON/OFF the machine
1
2 Bytes
I
C - - W U
DPT_Value_Temp
16ºC
–
32ºC
or ac. to param.
Setpoint
Value sent to the machine
2
1 Byte
I
C - - W U
DPT_HVACContrMode
0=Auto, 1=Heat
3=Cool, 9=Fan
14=Dry
Mode
0=Auto;1=Ht;3=Cool;9=Fan;14=Dry
3
1 Byte
I
C - - W U
DPT_Scaling
0%-50% Low
51%-100% High
Fan [1byte]
0-50%=Low;51-100%=High
1 Byte
I
C - - W U
DPT_Scaling
0%-33% Min.
34%-67% Med,
68%-100% Max.
Fan [1byte]
0-33%Min;34-67%Mid;>68%Max
4
1 Bit
I
C - - W U
DPT_Switch
0/1
Swing
0=Among fixed pos.;1=Motion
5
1 Bit
O
C T R - -
DPT_Switch
0/1
On/Off (status)
Machine State (ON/OFF)
6
2 Bytes
O
C T R - -
DPT_Value_Temp
16ºC
–
32ºC
or ac. to param.
Setpoint (status)
Value received from machine
7
1 Byte
O
C T R - -
DPT_HVACContrMode
0=Auto
…
14=Dry
Mode (status)
Current Mode: 0=Auto;1=Heat...
8
1 Byte
O
C T R - -
DPT_Scaling
33%/67%/100%
Fan [1 byte] (status)
33%Min;67%Mid;100%Max
1 Byte
O
C T R - -
DPT_Scaling
50%/100%
Fan [1 byte] (status)
50%Min;100%Max
9
1 Byte
O
C T R - -
DPT_Scaling
0% Posit. 1
20% Posit. 2
40% Posit. 3
60% Posit. 4
80% Posit. 5
100% In mot.
Swing [1byte] (status)
0-80%=Fixed pos.,100%=Motion
10
1 Bit
I
C T - W U
DPT_Switch
0/1
Auto Mode
1=Set Auto Mode;0=Nothing
11
1 Bit
I
C T - W U
DPT_Switch
0/1
Cool Mode
1=Set Cool Mode;0=Nothing