background image

 

 

 

HeatingBOX

 

http://www.zennio.com

 

               

Technical Support:

 

http://support.zennio.com

 

 

28 

2.5

 

MANUAL CONTROL 

HeatingBOX 

allows  controlling  the  outputs  through  the  pushbuttons  on  the  top  of  the  device. 

Each output has its associated pushbutton.  

Manual  operation  can  be  done  in  two  different  ways,  named  as 

Test  On  Mode 

(for  testing 

purposes during the configuration of the device) and 

Test Off Mode 

(for a normal use, anytime). 

Whether both, only one or none of these modes are available needs to be parameterised in ETS. 

Moreover, it is possible to enable a specific binary object for locking and unlocking the manual 

control in runtime.  

Note

:  

 

The 

Test Off mode

 will be active (unless it has been disabled by parameter) 

after  a  download  or  a  reset  with  no  need  of  a  specific  activation 

–  the 

pushbuttons will respond to user presses from the start.  

 

On  the  contrary,  switching  to  the 

Test  On  mode

  (unless  disabled  by 

parameter)  needs  to  be  done  by  long-pressing  the  Prog./Test  button  (for  at 

least three seconds), until the LED is no longer red and turns yellow. From that 

moment, once the button is released, the LED light will remain green to confirm 

that the device has switched from the Test Off mode to the Test On mode. After 

that, an additional press will turn the LED yellow and then off, once the button 

is released. This way, the device leaves the Test On mode. Note that it will also 

leave this mode if a bus power failure takes place.

 

 

The  manual  control  of  the  outputs  is  intended  to  perform  on/off  switches, 

independently  of  the  method  of  control  configured  (one-bit  or  one-byte).  In 

other words, it does allow testing the opening and closing of the valves, but 

intermediate positioning is not possible.

 

Test Off Mode 

Under the Test Off Mode, the outputs can be controlled through both their communication objects 

and  the  actual  pushbuttons  located  on  the  top  of  the  device.  Also,  during  this  manual  control 

mode, the control commands received by the bus will continue to be analysed and executed. 

Содержание HeatingBOX 24V 4X

Страница 1: ...HeatingBOX 24V 230V 4X 8X 4 Output 8 Output 24V 230V Heating Actuator USER MANUAL ZCL4HT24 ZCL8HT24 ZCL 4HT230 ZCL 8HT230 Application programme version 1 2 User manual edition 1 2 _a www zennio com...

Страница 2: ...ower Loss 6 2 Configuration 7 2 1 General 7 2 2 Thermostats 9 2 3 Logic Functions 10 2 4 Heating Controls 11 2 4 1 Heating Output n 15 2 4 1 1 Configuration 15 2 4 1 2 Alarms 20 2 4 1 3 Cyclical Monit...

Страница 3: ...s in the application programme New module Heartbeat New parameters o Value for open valve o Opening minimum value Output lock due to short circuit overload error Optimisation of thermostat and logic f...

Страница 4: ...V or 230V valves depending on the device The most outstanding features are 4 or 8 configurable outputs for controlling electromechanical valves A sole 230 VAC or 24 VAC VDC power input for all outputs...

Страница 5: ...ly analogous The main elements of the device are described next Test Prog Pushbutton 5 a short press on this button sets the device into the programming mode making the associated LED 5 light in red N...

Страница 6: ...es please refer to the corresponding Datasheet bundled with the original packaging of the device and also available at www zennio com 1 3 START UP AND POWER LOSS During the start up of the device and...

Страница 7: ...the General screen it is possible to activate deactivate all the required functionality ETS PARAMETERISATION Figure 2 General screen Heartbeat Periodic Alive Notification disabled enabled 1 incorporat...

Страница 8: ...n the left See section 2 2 for details Logic Function disabled enabled enables or disables the Logic Functions tab which contains specific parameters for the case the Logic Functions module is require...

Страница 9: ...ermostats depending on the device outputs number which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the HeatingBOX product sectio...

Страница 10: ...ion of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after executi...

Страница 11: ...ect HeatingBOX 230V reports both errors independently If a short circuit is detected at an output it will be periodically notified through a specific object of that output while overload error is repo...

Страница 12: ...k multiple actuators together and to determine the maximum of all of them The optional anti seize protection function which automatically switches the state of those outputs that have been in the same...

Страница 13: ...vents have been detected in a period of 3 minutes in any of the channels Three minutes after its activation the value 0 will be sent leaving the locking deactivated Notify When All Valves Are Closed d...

Страница 14: ...rmine the above maximum Resending Period 0 30 255 min Note this function ignores those outputs that have not been specifically marked for this purpose see section 2 4 1 Anti Seize Protection disabled...

Страница 15: ...ransformed into a PWM signal which is what the actuator actually applies to the output the period of which must be defined by the integrator while under a one bit control such period is assumed to be...

Страница 16: ...s on the valve type Valve type Value for Open Valve Control order Output power LED Valve state 1 bit 1 byte Normally closed 1 1 100 Yes Open 0 0 No Closed 0 0 100 Yes Open 1 0 No Closed Normally open...

Страница 17: ...orders to close value 0 and to open value 1 the valve must be received through the one bit object HCx Control Value 1 bit 1 byte the orders to close value 0 and to open value 100 the valve must be re...

Страница 18: ...s of the valve at the following control orders will be as follows Valve 0 control order 10 Valve 0 Valve 30 control order 10 Valve 20 Valve 0 alarm with action 15 Valve 0 Valve 50 alarm with action 15...

Страница 19: ...lue 0 when the output closes and the value 1 when it opens HCx Control Value 1 byte Status only for the one byte control it will send the current control value whenever it changes Note this object cor...

Страница 20: ...received at least once before the period expires note this check doesn t take place unless the object has been received at least once In case the object stops being refreshed i e the actuator does not...

Страница 21: ...onding checkbox Figure 9 Heating Control Alams Trigger 0 1 sets the value that when received from the KNX bus through object HCx Alarm will be interpreted by the actuator as an alarm trigger and will...

Страница 22: ...nd acknowledged if required The options depend on the control method 1 bit No Change Close Valve Open Valve Last Control Value Before the Alarm 1 byte No Change Specific Control Value Last Control Val...

Страница 23: ...ion tab section 2 4 1 1 the Cyclical Monitoring tab will be available containing the following parameters Figure 10 Heating Control Cyclical Monitoring Monitoring Interval 1 3600 s 1 30 1440 min 1 24...

Страница 24: ...it will recover the last status Custom start up the integrator may select whether the output is required to recover its previous status on the very first start up of the device it will remain closed...

Страница 25: ...mpose a delay 0 3600 s 0 1440 min 0 24 h to ensure that this value is sent once the other devices are ready to receive it Note This option is only available if Show Status Object is enabled from Confi...

Страница 26: ...curve will be defined as follows see Figure 13 and Figure 14 For control values lower than that of the first point the actual regulation value will be 0 For example in Figure 14 all control values un...

Страница 27: ...ion 2 4 1 1 a new tab will be incorporated into the tab tree on the left Figure 15 Heating Control Characteristic Curve Contains the parameters required to define up to three points of the characteris...

Страница 28: ...led by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer red and turns yellow From that moment once the button is released the LED...

Страница 29: ...ication objects will be ignored Short or long pressing the button will commute the on off state of the output The LED will light in green while the button is being hold The lock and alarm functions as...

Страница 30: ...anual Control disabled enabled unless the above parameter has been Disabled the Lock Manual Control parameter provides an optional procedure for locking the manual control in runtime When this checkbo...

Страница 31: ...65 95 125 155 185 215 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 Tx Effective Temperature Effective Control Temperature 6 36 66 96 126 156 186 216 1 Byte I C W DPT_HVACMode 1 Comfort 2 Standby 3...

Страница 32: ...PT_Heat_Cool 0 1 Tx Mode 0 Cool 1 Heat 22 52 82 112 142 172 202 232 1 Bit O C T R DPT_Heat_Cool 0 1 Tx Mode Status 0 Cool 1 Heat 23 53 83 113 143 173 203 233 1 Bit I C W DPT_Switch 0 1 Tx On Off 0 Off...

Страница 33: ...alue_4_Count LF Function x Result 4 bytes Signed 1 Byte O C T R DPT_Scaling 0 100 LF Function x Result 1 byte Percentage 2 Bytes O C T R DPT_Value_2_Count 32768 32767 LF Function x Result 2 bytes Sign...

Страница 34: ...enClose 0 1 HCx Control Value 1 bit 0 Open Valve 1 Close Valve 337 349 361 373 385 397 409 421 1 Bit O C T R DPT_Switch 0 1 HCx Control Value 1 bit Status 0 Closed 1 Open 1 Bit O C T R DPT_OpenClose 0...

Страница 35: ...00 670760 00 Tx Effective Temperature Effective Control Temperature 6 36 66 96 126 156 186 216 1 Byte I C W DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection Tx Special Mode 1 byte HVAC...

Страница 36: ...eat 23 53 83 113 143 173 203 233 1 Bit I C W DPT_Switch 0 1 Tx On Off 0 Off 1 On 24 54 84 114 144 174 204 234 1 Bit O C T R DPT_Switch 0 1 Tx On Off Status 0 Off 1 On 25 55 85 115 145 175 205 235 1 By...

Страница 37: ...lue_2_Count 32768 32767 LF Function x Result 2 Byte Signed 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 LF Function x Result 2 Byte Float 325 1 Bit O C T R DPT_Bool 0 1 HC All Valves Are Closed 0 F...

Страница 38: ...T R DPT_Switch 0 1 HCx Control Value 1 bit Status 0 Closed 1 Open 1 Bit O C T R DPT_OpenClose 0 1 HCx Control Value 1 bit Status 0 Open 1 Closed 338 350 362 374 386 398 410 422 1 Byte I C W DPT_Scali...

Страница 39: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Отзывы: