If the pushbutton on an
enabled output
is pressed, the output will behave as if an order to open
or to close the valve had been received through the corresponding communication object, and will
also send the status objects when required.
Regarding the lock and alarm functions, the device will behave under the Test Off mode as usual.
Button presses during this mode are entirely analogous to the reception of the corresponding
orders from the KNX bus.
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through the on-
board pushbuttons. Control orders received through communication objects will be ignored.
Short or long pressing the button will commute the on-off state of the output
. The LED will light
in green while the button is being hold.
The lock and alarm functions as well as any orders received from the KNX bus will not
have an effect over the output status while the device is under the Test On mode. The
status objects will not be sent to the bus, either.
On the contrary, the alarm and lock objects will be re-evaluated after leaving the Test On
mode, so any changes that may have taken place in Test On will be considered when
leaving.
Important
:
the device is delivered from factory with both manual modes (Test Off and
Test On) enabled by default
.
ETS PARAMETERISATION
After enabling “
Manual Control
” in the Configuration screen (see section 2.1), a new tab
will be incorporated into the tab tree on the left.
Figure 16.
Manual Control.
The only two parameters are: