HeatingBOX
http://www.zennio.com
Technical Support:
http://support.zennio.com
14
Maximum Control Value
[
disabled
/enabled
]: enables the 1-
byte object “
[HC]
Max. Control Value (Output)
”, which reports the maximum of the control
values of the outputs marked for this purpose (see section 2.4.1).
Figure 6.
Maximum control value.
Include External Value
[
disabled
/enabled
]: enables the 1-
byte object “
[HC]
Max. Control Value (Input)
” for the reception of an additional value which
will be taken into account to determine the above maximum.
Resending Period
[
0…
30
…255
][
min
].
Note
:
this function ignores those outputs that have not been specifically
marked
for this purpose (see section 2.4.1).
Anti-Seize Protection
[
disabled
/enabled
]: enables or disables the anti-seize
protection function.
The “
[HCx] Anti-Seize Protection
” binary object will send
the value “1” when the anti-seize process is triggered for output “x”, and the
value “0” when it is over.
Figure 7.
Heating Controls
– Anti-Seize Protection.
Periodicity
[
1…
7
…30
][
day
]: sets the maximum time an output can remain
still.
Duration
[
1…
5
…255
][
min
]: sets for how much time the output should switch
its position, in case it has been still for more than the above periodicity.