HeatingBOX
http://www.zennio.com
Technical Support:
http://support.zennio.com
12
the state of the other valves is not taken into account) and also
delayed
, to
ensure that such situation is not transitory and persists in time.
Maximum control
value
object, which reports (with a configurable periodicity)
the maximum of the current control values of the outputs that may have been
marked for such purpose. An
external
value (i.e., received through a specific
object) can be also considered for this comparison, which brings the option to
link multiple actuators together and to determine the maximum of all of them.
The optional
anti-seize
protection function, which automatically switches the
state of those outputs that have been in the same position for more than a
configurable time. After a certain duration (also configurable), they return to
their previous state.
ETS PARAMETERISATION
Figure 4.
Heating Controls
– Configuration (HeatingBOX 8X).
From the “Configuration” screen is possible to enable/disable all the common functions
required. In addition, each output can be individually enabled.
Startup Delay
[
0
…255
][
s
]
:
delay after the device initialisation.
Short Circuit/Overload Error Notification
[
disabled
/enabled
]
:
when enabled,
the following one-bit objects will be available: