Mode
[
Disabled / Only with Test Mode Off / Only with Test Mode On /
Test Off
Mode + Test On Mode
].
Depending on the selection, the device will permit using the manual control
under the Test Off, the Test On, or both modes. Note that, as stated before,
using the Test Off mode does not require any special action, while switching to
the Test On mode does require long-pressing the Prog./Test button.
Lock Manual Control
[
disabled
/enabled
]: unless the above parameter has
been “Disabled”, the Lock Manual Control parameter provides an optional
procedure for locking the manual control in runtime. When this checkbox is
enabled, object “
Lock Manual Control
” turns visible, as well as two more
parameters:
Value
[
0 = Unlock; 1 = Lock
/ 0 = Lock; 1= Unlock
]: defines whether the
manual control lock/unlock should take place respectively upon the
reception (through the aforementioned object) of values “0” and “1”, or the
opposite.
Initialization
[
Unlocked / Locked /
Last Value (Before Bus Failure)
]: sets
how the manual control should remain after the device start-up (after an ETS
download or a bus power failure).