HeatingBOX 24V
:
“
[HCx] Short Circuit/Overload Error
”, one for each
output.
HeatingBOX 230V
:
“
[HCx] Short Circuit Error
”, one for each output, and
“
[HCx-y] Overload Error
” one for outputs 1-4 and one for outputs 5-8; the
latter only in HeatingBOX 230V 8X.
These objects will be sent to the bus with the
value ‘1’ every 30 seconds as
long as the error persists,
and with the value ‘0’ (once) when the error is
over.
In addition, for both devices, the object
“
[CC] Short Circuit/Overload Lock
”,
common to all output, will be enabled. This object will be sent with value “1”
when at least 4 error events have been detected in a period of 3 minutes in any
of the channels. Three
minutes after its activation, the value “0” will be sent,
leaving the locking deactivated.
Notify When All Valves Are Closed
[
disabled
/enabled
]
:
if enabled, it provides
the one-bit object
“
[HC] All Valves are Closed
”, which will be sent to the bus
with a configurable value, depending on whether are valves are found to be
closed or not. A
delay
can be parameterised to ensure the persistence of this
situation.
Note
:
this function ignores those outputs that have not been specifically
marked
for this purpose (see section 2.4.1)
.
Figure 5.
Notify when all valves are closed.
Value
[
Send 0
/ Send 1
].
Delay
[
0…
30
…1440
][
min
] [
0…24
][
h
].
Note
:
this delay must be greater than the cycle time (either in case of making
use of an external device or of the 1-byte control method). See section 2.4.1.