1.1K~3.3KTL-G3
User manual
- 29 -
Make sure the grid is disconnected before removing the AC connector
Caution
Mode
Ⅱ
connector installation
instructions
Step 1
Select appropriate cables
according to Table 4-2, Remove the
insulation layer of the AC output cable
using a wire stripper according to the
figure shown below: A:15-25mm
B:6~8mm
Figure 4-18
Step 2
Disassemble the AC connector
according to the figure shown below: insert
the AC output cable (with its insulation
layer stripped according to step 1) through
the waterproof locking cable gland.
Figure 4-19
Step 3
Connect AC output cable as per the following requirements:
Connect the yellow-green wire to the hole labeled "PE", fasten the wire using an Cross
screwdriver;
Connect the brown wire to the hole labeled "L", fasten the wire using an Cross
screwdriver;
Connect the blue wire to the hole labeled "N", fasten the wire using an Cross screwdriver.