AFDZP0BA – VCM Zapi 2uC - User Manual
Page - 45/54
board.
15) VALVE ENABLE
Cause:
It occurs when the uC master try to activate an output but the supervisor uC
doesn’t activate the enable.
Troubleshooting:
Check if some alarm is present on supervisor uC. Otherwise a fault in the
hardware is present, the board must be replaced.
16) NO CAN MSG 5
Cause:
Timeout on the local CAN BUS
Troubleshooting:
Switch OFF and ON. If the alarm is still present replace the board.
17) WAITING FOR NODE
Cause:
The controller receives from the CAN the message that another controller in
the net is in fault condition; as a consequence the VCM controller itself
cannot enter an operative status, but has to WAIT for the other controller
coming out from the fault status.
18) CONTROLLER MISM
Cause:
Wrong customer ID code found in the protected area of memory where this
parameter are stored
Troubleshooting:
Replaced the controller.
19) PUMP IN ALARM
Cause:
Alarm on pump controller.
Troubleshooting:
Check the alarm on pump controller.
20) NO CAN MSG 14
Cause:
No CAN message from pump controller
Troubleshooting:
Check the CAN connection on pump controller side. Verify that the pump
communicates on CAN bus
21) NO CAN MSG A
Cause:
No CAN message from the Mini Lever or Joystick
Troubleshooting:
Check the CAN connection on Mini Lever or Joystick side. Verify that the Mini
Lever or Joystick communicate on CAN bus
22) SDO TRAC
Cause
:
There is a problem in the communication of HM between VCM and traction
Troubleshooting: Verify the communication between the two controllers. If all
is ok try to replace the board.