3.8.2 Procedure
Cooling mode: refer to “the oil return procedure in cooling mode”
Heating mode: refer to “the oil return procedure in heating mode”
3.8.3 The protection treatment in oil return operation:
In the course of cooling oil return, because of all kinds of protection or abnormal unit stop,
after the unit restart, the time will not be cleared, the system need another oil return operation.
In the refrigerant flow course in oil return of cooling mode or after oil return, and within 5
minutes after the refrigerant being eliminated is over, the anti-freeze protection and low
pressure protection are invalid, other protection is valid.
In the course of heating oil return ,because of all kinds of protection or abnormal unit stop, the
system need not another oil return operation after the unit stop for 3 minutes and enter in
heating mode directly. In the course of changing to cooling oil return, the anti-freeze
protection and low pressure protection are invalid, other protection is valid.
Oil return procedure in cooling mode:
Quit condition of oil return:
1 minute later after oil return is over
&
Td
‐
Tcm
>
30
℃
OR
OR
Ts
‐
Tc
>
30
℃
Tc
<
‐
35
℃
Max. 10 minutes
Oil return procedure in heating mode:
Send oil return signal
oil return beginning
oil return over
60
秒
ref.eliminated 30s
80 Hz
(
E
)
40HZ
(
E
)
Inverter compressor auto FQY
300pulse
(
E
)
outdoor unit PMV
auto open angle
auto open angle
120pulse
(
E
)
Outdoor fan motor
auto operation
auto
(
TC or ambient control
)
auto operation
running indoor motor auto operation
auto
(
set fan speed
)
auto operation
stop indoor motor stop
stop
stop
4-way valve
OFF
OFF
OFF
109
Содержание YHKJXH012BAM--FX
Страница 34: ...Model W D H L1 L2 L3 YHUJYH024BAR A X 860 308 730 633 113 5 340 YHUJYH024BAR A X 34...
Страница 36: ...YHFJZH012BAM AFX YHFJZH018BAM AFX YHFJZH024BAR AFX 3 33 100 22 1 1 0 1 0 0 33 36...
Страница 39: ...800 1320 830 1200 170 270 250 365 185 250 60 45 1105 4 758 2 15 88 YHGJXH048 60BAR GX YHEJXH028 36 48BAR GX 39...
Страница 93: ...YHUJYH024BAR A X power module YHUJYH028 36BAR A X power module 93...
Страница 94: ...YHUJYH028 36BAR A X filter board YHUJYH028 36 48BAR A X YHUJYH048BAS A X YHUJYH060BAS A X PCB 0151800054A 94...
Страница 95: ...YHUJYH048BAS A X YHUJYH060BAS A X power module YHUJYH048BAS A X YHUJYH060BAS A X filter board 95...
Страница 96: ...YHUJYH048BAR A X filter board YHUJYH048BAR A X power module 96...
Страница 111: ...5 2 Indoor unit 5 2 1 PCB 0151800106 for 28 36 48 60 indoor unit 111 YHDJXH018BAM GX...
Страница 151: ...151...